2 Instructions

2-60

CP1E CPU Unit Instructions Reference Manual(W483)

Timer and Counter Instructions

Refresh Methods for Timer/Counter PV

Overview

There are two PV refresh methods for instructions related to timer/counters, “BCD” and “BINARY”.

The PLC Setup for all of the timer/counter-related instructions. The refresh method is valid also when
setting an SV indirectly (i.e., using the contents of memory word). (That is, the contents of the
addressed word is taken as either BCD or binary data according to the refresh method that is set.)

Applicable Instructions

Setting method for PV refresh

BCD and binary PV refreshing can both be used in the same project. The setting of the PV refresh
method in the PLC Setup will be ignored.

Basic Timer Specifications

Method

Description

Setting range

Set value

BCD

Sets the timer set value in BCD.

0~9.999

#0000~9999

Binary

Sets the timer set value in BINARY.

0~65.535

&0~65535 or #0000~FFFF

Classification

Instruction

Mnemonic

BCD

Binary

Timer/counter
instructions

HUNDRED-MS TIMER

TIM

TIMX(550)

TEN-MS TIMER

TIMH(015)

TIMHX(551)

ONE-MS TIMER

TMHH(540)

TMHHX(552)

ACCUMULATIVE TIMER

TTIM(087)

TTIMX(555)

LONG TIMER

TIML(542)

TIMLX(553)

COUNTER

CNT

CNTX(546)

REVERSIBLE COUNTER

CNTR(012)

CNTRX(548)

RESET TIMER/COUNTER

CNR(545)

CNRX(547)

Item

TIM/TIMX
(550)

TIMH(015)/
TIMHX(551)

TMHH(540)/
TMHHX(552)

TTIM(087)/
TTIMX(555)

TIML(542)/
TIMLX(553)

Timing method

Decrementing

Decrementing

Decrementing

Incrementing

Decrementing

Timing units

100 ms

10 ms

1 ms

100 ms

100 ms

Maximum SV

TIM: 999.9 s

TIMX: 6,553.5 s

TIMH: 99.99 s

TIMHX: 655.35 s

TMHH: 9.999 s

TMHHX: 65.535 s

TTIM: 999.9 s

TTIMX: 6,553.5 s

TIML:115 days

TIMLX: 49,710 days

Outputs/instruction

1

1

1

1

1

Timer numbers

Used

Used

Used

Used

Not used

Completion Flag refresh-
ing

When the instruction
is executed

When the instruction is
executed

When the instruction is
executed

When the instruction is
executed

When the instruction is
executed

Timer PV refreshing
(See note)

When the instruction
is executed

When the instruction is
executed

When the instruction is
executed

When the instruction is
executed

When the instruction is
executed

Value after
reset

Completion
Flags

OFF

OFF

OFF

OFF

OFF

PVs

SV

SV

SV

0

SV