Cnr/cnrx, Applicable program areas operands, Flags function – Omron SYSMAC CP CP1E-N@@D@-@ User Manual
Page 122: 2 instructions, N1: first number in range, N2: last number in range, Operand specifications
2 Instructions
2-86
CP1E CPU Unit Instructions Reference Manual(W483)
CNR/CNRX
Applicable Program Areas
Operands
N1: First Number in Range
N1 must be a timer number between T000 and T255 or a counter number between C000 and C255.
N2: Last Number in Range
N2 must be a timer number between T000 and T255 or a counter number between C000 and C255.
Operand Specifications
Flags
Function
CNR(545)/CNRX(547) resets the Completion Flags of all timers or counters from N1 to N2. At the same
time, the PVs will all be set to the maximum value (9999 for BCD and FFFF for binary). (The PV will be
set to the SV the next time that the timer or counter instruction is executed.)
Instruction
Mnemonic
Variations
Function
code
Function
RESET TIMER/COUNTER
CNR
@CNR
545
Resets the timers or counters within the specified
range of timer or counter numbers.
CNRX
@CNRX
547
Symbol
CNR
CNRX
BCD
Binary
Area
Step program areas
Subroutines
Interrupt tasks
Usage
OK
OK
OK
Operand
Description
Data type
Size
CNT
CNTX
N1
First number in range
TIMER/COUNTER
*1
Variable
N2
Last number in range
TIMER/COUNTER
*1
Variable
Area
Word addresses
Indirect DM addresses
Constants
CF
Pulse bits
TR bits
CIO
WR
HR
AR
T
C
DM
@DM
*DM
N1,N2
---
---
---
---
OK
OK
---
---
---
---
---
---
---
Name
Label
Operation
Error Flag
P_ER
• ON if N1 and N2 are not in the same data area.
• OFF in all other cases.
CNR(545)
N1
N2
N1: First number in range
N2: Last number in range
CNRX(547)
N1
N2
N1: First number in range
N2: Last number in range