Fals, Applicable program areas operands, Flags – Omron SYSMAC CP CP1E-N@@D@-@ User Manual
Page 429: 2 instructions, Generating user-defined fatal errors, Generating fatal errors from the system, Operand specifications
2-393
2 Instructions
CP1E CPU Unit Instructions Reference Manual(W483)
F
ailu
re Dia
gn
osis I
n
stru
ctio
ns
2
F
A
L
S
FALS
Applicable Program Areas
Operands
Generating User-defined Fatal Errors
Note The value of operand N must be different from the content of A529 (the system-generated FAL/FALS number).
Generating Fatal Errors from the System
The following table shows the function of the operands.
Note The value of operand N must be the same as the content of A529 (the system-generated FAL/FALS number).
Operand Specifications
Flags
Instruction
Mnemonic
Variations
Function
code
Function
SEVERE FAILURE ALARM
FALS
---
007
Generates user-defined fatal errors. Fatal errors
stop PLC operation.
Symbol
FALS
Generating User-defined Fatal Errors
Generating Fatal System Errors
Area
Step program areas
Subroutines
Interrupt tasks
Usage
OK
OK
OK
Operand
Description
Data type
Size
N
FAL number
Constants only
1
S
First message word or constant / First word containing the error
code and error details
WORD
Variable
Generates a non-fatal error
N
1 to 511 (These FALS numbers are shared with FALS numbers.)
S
Specifies the first of eight words containing an ASCII message to be displayed on the Programming Device.
Specify a constant (0000 to FFFF) if a message is not required.
Generates a non-fatal error
N
1 to 511 (These FALS numbers are shared with FAL numbers.)
S
Error code that will be generated. (See Description below.)
S+1
Error details code that will be generated. (See Description below.)
Area
Word addresses
Indirect DM addresses
Constants
CF
Pulse bits
TR bits
CIO
WR
HR
AR
T
C
DM
@DM
*DM
N
---
---
---
---
---
---
---
---
---
OK
---
---
---
S
OK
OK
OK
OK
OK
OK
OK
OK
OK
Name
Label
Operation
Error Flag
P_ER
• ON if N is not within the specified range of 0001 to 01FF (1 to 511 decimal).
• ON if a fatal system error is being generated, but the specified error code or error details code is
incorrect.
• OFF in all other cases.
N: FAL number
S: First message word or
FALS(007)
N
S
constant (0000 to FFFF)
N: FAL number (value in A529)
S: First word containing the
FALS(007)
N
S
error code and error details