beautypg.com

2 instructions – Omron SYSMAC CP CP1E-N@@D@-@ User Manual

Page 298

background image

2 Instructions

2-262

CP1E CPU Unit Instructions Reference Manual(W483)

Note 1 When the unit is designated as 1, the range is from 1 to 8,191 times the period. When the unit is designated as 9, the

range is from 0.1 to 819.1 s. When 9 is designated, set the integral and derivative times to within a range of 1 to 8,191
times the sampling period.

2 Setting the 2-PID parameter (

α) to 000 yields 0.65, the normal value.

3 When the manipulated variable output limit control is enabled (i.e., set to “1”), set the values as follows:

0000

≤ MV output lower limit ≤ MV output upper limit ≤ Max. value of output range

Bit 00 of C+5

PID forward/reverse
designation

Determines the direction of the proportional
action.

0:

Reverse action

1:

Forward action

Not allowed

Bit 12 of C+6

Manipulated variable
output limit control

Determines whether or not limit control will apply
to the manipulated variable output.

0:

Disabled (no limit control)

1:

Enabled (limit control)

Bits 08 to 11
of C+6

Input range

The number of input data bits.

0: 8 bits

5: 13 bits

1: 9 bits

6: 14 bits

2: 10 bits

7: 15 bits

3: 11 bits

8: 16 bits

4: 12 bits

Bits 04 to 07
of C+6

Integral and deriva-
tive unit

Determines the unit for expressing the integral
and derivative constants.

1:

Sampling period multiple

9:

Time (unit: 100 ms)

Bits 00 to 03
of C+6

Output range

The number of output data bits. (The number of
output bits is automatically the same as the num-
ber of input bits.)

0: 8 bits

5: 13 bits

1: 9 bits

6: 14 bits

2: 10 bits

7: 15 bits

3: 11 bits

8: 16 bits

4: 12 bits

C+7

Manipulated variable
output lower limit

The lower limit for when the manipulated variable
output limit is enabled.

0000 to FFFF (binary)
(See note 3.)

C+8

Manipulated variable
output upper limit

The upper limit for when the manipulated variable
output limit is enabled.

0000 to FFFF (binary)
(See note 3.)

Bit 15 of C+9

AT Command Bit

This control bit starts autotuning.

Set the AT Command Bit to 1 to perform auto-

tuning. (Autotuning can be started while
PIDAT(191) is being executed.)

This bit is turned OFF automatically when auto-

tuning is completed.

Autotuning will be interrupted if the AT Command
Bit is turned OFF manually. In this case, the PID
constants will be enabled if they were already cal-
culated when autotuning was interrupted.

As a Control Bit:

0

1:

Executes autotuning.

1

0:

Interrupts autotuning.
(PID(191) turns the bit OFF automatically
when autotuning is completed.

As a Flag:
0:

Autotuning is not being executed.

1:

Autotuning is being executed.

Allowed

Bits 00 to 11
of C+9

AT Calculation Gain

Set this parameter to adjust the contribution of the
PID calculation results to the stored values.
Normally, leave this parameter set to its default
(0000).

Increase the value when emphasizing stability.

Decrease the value when emphasizing respon-

siveness.

0000 hex: 1.00 (Default)
0001 to 03E8 hex (1 to 1000);
(0.01 to 10.00, in units of 0.01)

Allowed
(These parameters
are read when
autotuning starts.)

C+10

Limit-cycle Hysteresis

Sets the hysteresis when the limit cycle is gener-
ated. The default setting for reverse operation
turns ON the MV with a hysteresis of SV

−20%.

Increase this setting if a proper limit cycle cannot
be generated because the PV is unstable. How-
ever, the AT accuracy will decline if the Limit-cycle
Hysteresis is higher than necessary.

0000 hex: 0.20% (Default)
0001 to 03E8 hex:
0.01 to 10.00% in units of 0.01%
FFFF hex: 0.00%

Note The percentage is with respect to the

input range.

Control data

Item

Contents

Setting range

Change with ON

input condition

This manual is related to the following products: