Hint, Precautions, 2 instructions – Omron SYSMAC CP CP1E-N@@D@-@ User Manual

Page 413: Start code/end code settings and receive data

background image

2-377

2 Instructions

CP1E CPU Unit Instructions Reference Manual(W483)

Serial Co

mm

un
icatio

n

In

stru

ctio

ns

2

RXD

Start Code/End Code Settings and Receive Data

Hint

When RXD(235) is used to read data that was received at one of the Serial Option Board’s ports , the

port’s reception buffer is cleared after RXD(235) is executed. Consequently, RXD(235) can not be
executed repeatedly to read a block of data in parts.

Precautions

RXD(235) can be used only for the CPU Unit’s RS-232C port or the Serial Option Board port. In addi-

tion, the port must be set to no-protocol mode.

Execute this instruction when the reception completion flag (RS-232C incorporated in the CPU unit:

A392.06, Serial Option Board: A392.14) is 1 (ON) to receive data (from the reception buffer).

When data is received, the data must be read by an RXD instruction or the next data cannot be

received. When the reception completion flag turns ON, read the received data with an RXD instruc-
tion before the next reception.

Specify the size of the receive data, not including the start code and end code, in N.

If 0 is specified for N, the Reception Completed Flag and Reception Overflow Flag (note(a)) will be

turned OFF, the Reception Counter (note(b)) will be cleared to 0, and nothing will be stored in memory.

1 2 3 4 5 6 0...

1 2 3 4 5 6 0...

1 2 3 4 5 6 0...

1 2 3 4 5 6 0...

1 2 3 4 5 6 0...

1 2 3 4 5 6 0...

1

3

5

2

4

6

1

3

5

2

4

6

1

2

3

4

5

6

LF

CR

Bytes

Receive bytes: Specified
in the PC Setup

Receive bytes after ST:
Specified in the PC Setup

Receive bytes before
ED: 256 max.

Receive bytes between
ST and ED: 256 max.

Receive bytes before
CR+LF: 256 max.

Receive bytes between
ST and CR+LF: 256 max.

When receiving the most significant
bytes first is specified (0):

Most signifi-
cant bytes

Least signif-

icant bytes

When receiving the least significant
bytes first is specified (1):

Most signifi-
cant bytes

Least signif-
icant bytes

N bytes
stored in the
specified

Max: 256 bytes order.

Received

CPU Unit’s built-in RS-232C port
or Serial Option Board port

Start and CR+LF End Code

CR+LF End Code

Start and End Code

Only End Code

Only Start Code

No Start or End Code

ED

ST

ED

ST

ST

CR

LF

D

D+1

D+2

15

7

0

8

D

D+1

D+2

15

7

0

8