High-speed counter/pulse output instructions, Applicable program areas operands, 2 instructions – Omron SYSMAC CP CP1E-N@@D@-@ User Manual

Page 344: P: port specifier

background image

2 Instructions

2-308

CP1E CPU Unit Instructions Reference Manual(W483)

High-speed Counter/Pulse Output
Instructions

INI

Applicable Program Areas

Operands

P: Port Specifier

Instruction

Mne-

monic

Varia-

tions

Function

code

Function

MODE CONTROL

INI

@INI

880

INI(880) can be used to execute the following operations

To start comparison with the high-speed counter comparison table

To stop comparison with the high-speed counter comparison table

To change the PV of the high-speed counter.

To change the PV of interrupt inputs in counter mode.

To change the PV of the pulse output (origin fixed at 0).

To stop pulse output.

Symbol

INI

Area

Step program areas

Subroutines

Interrupt tasks

Usage

OK

OK

OK

Operand

Description

Data type

Size

P

Port specifier

WORD

1

C

Control data

UINT

1

NV

First word with new PV

DWORD

2

P

Port

0000 hex

Pulse output 0

0001 hex

Pulse output 1

0010 hex

High-speed counter 0

0011 hex

High-speed counter 1

0012 hex

High-speed counter 2

0013 hex

High-speed counter 3

0014 hex

High-speed counter 4

0015 hex

High-speed counter 5 (Cannot be used in CP1E-E10D - )

1000 hex

PWM(891) output 0

NV: First word with new PV

INI(880)

P

C

NV

P: Port specifier

C: Control data