beautypg.com

Xfer, Applicable program areas operands, Flags – Omron SYSMAC CP CP1E-N@@D@-@ User Manual

Page 153: 2 instructions, N: number of words, Operand specifications

background image

2-117

2 Instructions

CP1E CPU Unit Instructions Reference Manual(W483)

D
a

ta Mo

vem

ent I

n

stru

ctio

ns

2

XFER

XFER

Applicable Program Areas

Operands

N: Number of Words

Specifies the number of words to be transferred. The possible range for N is 0000 to FFFF (0 to
65,535 decimal).

Operand Specifications

Flags

Instruction

Mnemonic

Variations

Function

code

Function

BLOCK TRANSFER

XFER

@XFER

070

Transfers the specified number of consecutive
words.

Symbol

XFER

Area

Step program areas

Subroutines

Interrupt tasks

Usage

OK

OK

OK

Operand

Description

Data type

Size

N

Number of words

UINT

1

S

First source word

WORD

Variable

D

First destination word

WORD

Variable

Area

Word addresses

Indirect DM addresses

Constants

CF

Pulse bits

TR bits

CIO

WR

HR

AR

T

C

DM

@DM

*DM

N

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

---

---

---

S, D

---

Name

Label

Operation

Error Flag

P_ER

OFF

XFER(070)

N

S

D

N: Number of words

S: First source word

D: First destination word

15

0

S

S+(N-1)

to

15

0

D

D+(N-1)

to

This manual is related to the following products: