11.2.1 Selection of MCCB and Ground Fault Interrupter
11 - 4
11.2 Specifications of Options and Peripheral Devices
11.2.1 Selection of MCCB and Ground Fault Interrupter
Be sure to install an MCCB or ground fault interrupter on the power supply side in order to protect the Invert-
er wirings.
When using an MCCB, use one that has the sensitivity current of 200 mA min. and operation time of 0.1 s
min. and also that incorporates countermeasures against harmonics.
The following tables show MCCB selection examples.
J
400-V Class Inverters
VS-616G5 Model
CIMR-G5Aj
Output Capacity
(kVA)
Rated Output Cur-
rent (A)
MCCB Model
Rated Current (A)
4200
320
414
NF600
600
4400
610
800
NF1200
1200
4600
910
1200
NF2000
1800
4800
1200
1600
NF2500
2500
J
575-V Class Inverters
VS-616G5 Model
CIMR-G5Aj
Output Capacity
(kVA)
Rated Output Cur-
rent (A)
MCCB Model
Rated Current (A)
5300
410
414
NF600
600
5600
800
800
NF1200
1200
5900
1200
1200
NF2000
1800
512C
1600
1600
NF2500
2500