Basic Operation
6.5.2 V/f Pattern Selection: E1-03
6 - 40
6.5.2 V/f Pattern Selection: E1-03
D
The V/f pattern can be set to any of the following:
•
One of 15 preset patterns (settings 0 through E)
•
A custom user-set pattern (setting F)
D
The factory setting for E1-03 is “F” (user-defined V/f pattern), but the default contents of this setting
are the same as setting “1.”
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
E1-03
V/f pattern selection
x
0 to F
--
F
Q
Q
x
x
J
Selecting a Preset V/f Pattern: E1-03 = “0” through “E”
D
Refer to the following table when selecting one of the 15 preset patterns.
Characteristics
Applications
Setting
Specifications
These patterns are for general-purpose
applications
0
50 Hz
Fixed torque
p
g
p p
applications.
Use these patterns when the load torque
1
60 Hz
Fixed torque
Use these patterns when the load torque
is to remain constant for any rotational
speed such as in straight-line convey-
2
60 Hz, Voltage saturation at 50 Hz
speed, such as in straight-line convey-
ors.
3
72 Hz, Voltage saturation at 60 Hz
U th
tt
h
th
i
4
50 Hz, cubic
Variable torque
Use these patterns when there is a qua-
dratic or cubic relationship between the
5
50 Hz, quadratic
Variable torque
dratic or cubic relationship between the
rotational speed and load, such as in fans
or pumps
6
60 Hz, cubic
or pumps.
7
60 Hz, quadratic
Select a high starting torque V/f pattern
only in the following cases:
S
The wiring distance between the In-
8
50 Hz, low starting torque
High starting
S
The wiring distance between the In-
verter and motor is relatively large
(greater than 150 m).
S
A large torque is required at startup
9
50 Hz, high starting torque
High starting
torque *
S
A large torque is required at startup
(such as heavy axis loads).
S
An AC or DC reactor is connected to
the Inverter’s input or output
A
60 Hz, low starting torque
the Inverter’s input or output.
S
A motor less than the maximum appli-
cable motor is being used.
b
60 Hz, high starting torque
Hi h
d
These patterns are for applications that
f
i
h
C
90 Hz, Voltage saturation at 60 Hz
High-speed op-
erations
These patterns are for applications that
must rotate at frequencies greater than
60 Hz. A fixed voltage is applied at fre-
d
120 Hz, Voltage saturation at 60 Hz
erations
60 Hz. A fixed voltage is applied at fre-
quencies greater than 60 Hz.
E
150 Hz, Voltage saturation at 60 Hz
* Normally it isn’t necessary to use these patterns because starting torque isensured byautomatic
torque boost functions.
D
The constant settings for E1-04 through E1-10 will be changed automatically when one of these patterns
is selected.
D
The characteristics for these patterns are shown in the diagrams on page 6 - 23.
J
Setting a User-defined V/f Pattern: E1-03 = “F”
D
Constants E1-04 through E1-10 can be set by the user when E1-03 has been set to “F.”
D
Refer to page 6 - 24 for details on setting these constants.