6.4 Flux Vector Control
6 - 29
6.4.2 Setting the Zero-speed Operation Constants
D
With flux vector control, operation is possible even when the frequency reference is zero (below the
minimum output frequency).
D
Set the operation methods for the minimum output frequency.
J
Stopping Method Selection: b1-03
D
Set the stopping method used when a stop command is input.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
b1-03
Stopping method
selection
x
0 to 3
--
0
Q
Q
Q
Q
D
Settings
Setting
Function
0
Deceleration to stop
1
Coast to stop
2
DC injection braking stop (This setting can’t be made with flux vector control.)
3
Coast to stop with timer (This setting can’t be made with flux vector control.)
J
Zero-speed Operation: b1-05 and Minimum Output Frequency: E1-09
D
Set the operation method used when the frequency reference is below the minimum output frequency.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
b1-05
Operation selection
for setting of E1-09 or
less
x
0 to 3
--
0
x
x
x
A
D
Settings
Setting
Function
0
Operate according to the frequency reference. (E1-09 is invalid.)
1
Interrupt the output. (Coast when the frequency reference is below E1-09.)
2
Operate at E1-09 frequency. (Output the frequency set in E1-09.)
3
Zero-speed operation (Zero reference value when the frequency reference is below E1-09.)
Minimum Output Frequency (FMIN): E1-09
D
Set the minimum output frequency according to the requirements of the application.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
E1-09
Min. output frequency
x
0.0 to 150.0
Hz
0.0
Q
Q
Q
A
J
Initial Excitation Settings: b2-01, b2-03, b2-04
D
Set the zero speed level, DC injection braking time at startup, and the DC injection braking time when
stopping.
6