Yaskawa G5HHP Drive User Manual
Page 293

8.2 Programming Mode Constants
8 - 27
* The values in parentheses indicate initial values when initialized in 3-wire sequence.
Multi-function Input Functions
Control Methods
Setting
value
Function
V/f
V/f
w/
PG
Open
loop
Vector
Flux
vector
Page
0
3-wire sequence (Forward/Reverse run command)
f
f
f
f
6 - 14
1
Local/Remote selection (ON: Operator, OFF: Constant setting)
f
f
f
f
7 - 63
2
Option/Inverter selection (ON: Option card)
f
f
f
f
7 - 63
3
Multi-step speed reference 1
When H3-05 is set to “0,” this function is combined with “Master/auxiliary speed switch.”
f
f
f
f
6 - 14
4
Multi-step speed reference 2
f
f
f
f
6 - 14
5
Multi-step speed reference 3
f
f
f
f
6 - 14
6
Jog frequency reference (higher priority than multi-step speed reference)
f
f
f
f
6 - 14
7
Accel/Decel time 1
f
f
f
f
6 - 17
8
External baseblock NO (NO contact: Baseblock at ON)
f
f
f
f
7 - 64
9
External baseblock NC (NC contact: Baseblock at OFF)
f
f
f
f
7 - 64
A
Accel/Decel ramp hold (ON: Accel/decel stopped, frequency on hold)
f
f
f
f
7 - 64
B
OH2 alarm signal input (ON: OH2 will be displayed)
f
f
f
f
7 - 65
C
Multi-function analog input selection (ON: Enable)
f
f
f
f
7 - 65
D
No V/f control with PG (ON: Speed feedback control disabled,) (normal V/f control)
f
f
x
x
7 - 65
E
Speed control integral reset (ON: Integral control disabled)
x
f
x
f
7 - 65
F
Not used. (Do not input this setting.)
--
--
--
--
--
10--
Up command (Always set with the down command)
f
f
f
f
7 - 67
11
Down command (Always set with the up command)
f
f
f
f
7 - 67
12
FJOG command (ON: Forward run at jog frequency d1-09)
f
f
f
f
6 - 17
13
RJOG command (ON: Reverse run at jog frequency d1-09)
f
f
f
f
6 - 17
14
Fault reset (Reset when turned ON)
f
f
f
f
7 - 68
15
Emergency stop (ON: Deceleration to stop in emergency stop time C1-09)
f
f
f
f
6 - 17
16
Motor switch command (Motor 2 selection)
f
--
f
--
7 - 68
18
Timer function input (Functions are set with b4-01, b4-02 and the timer function is set at the
same time)
f
f
f
f
7 - 43
19
PID control disable (ON: PID control disabled)
f
f
f
f
7 - 69
1A
Accel/Decel time 2
f
f
f
f
6 - 17
1B
Constants write enable (ON: All constants can be written-in. OFF: All constants other than fre-
quency monitor are write protected.)
f
f
f
f
7 - 69
1C
Trim control increase (ON: d4-02 frequencies are added to analog frequency references.)
f
f
f
f
7 - 69
1D
Trim control decrease (ON: d4-02 frequencies are subtracted from analog frequency references.)
f
f
f
f
7 - 69
1E
Analog frequency reference sample/hold
f
f
f
f
7 - 71
1F
Frequency reference terminal 36/39 selection (ON: selects terminal 39)
f
f
f
f
6 - 17
20 to 2F
External fault (Desired settings possible)
Input mode: NO contact/NC contact, Detection mode: Normal/during operation
Stopping method: Deceleration to stop, coast to stop, emergency stop or continue operation.
f
f
f
f
7 - 71
30
PID control integral reset (ON: Reset)
f
f
f
f
--
60
DC injection braking command (ON: Performs DC injection braking)
f
f
f
f
7 - 74
61
External speed search command 1: Maximum output frequency (ON: speed search)
f
x
f
x
7 - 74
62
External speed search command 2: Set frequency (ON: speed search)
f
x
f
x
7 - 74
63
Energy-saving command (ON: Energy-saving control set for b8-01, b8-02)
f
f
x
x
7 - 12
8