Basic Operation

6.5.5 Adjusting Speed Control (ASR) Gain

6 - 46

4. If the overshooting or undershooting can’t be eliminated by adjusting the gain, decrease the ASR limit

(C5-05) to lower the frequency reference compensation limit.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

C5-05

ASR limit

x

0.0 to 20.0

%

5.0

x

A

x

x

Since C5-05 can’t be changed during operation, stop the Inverter’s operation and then decrease the

ASR limit by 0.5 (%).

Perform step 3 again after the setting has been changed.

The ASR limit is the frequency limit for compensation by speed control. Set this frequency limit

as a percentage of the maximum output frequency.

If the frequency limit is lowered too much, the motor speed might not reach the target speed. Verify

that the target speed is reached during normal operation.