Yaskawa G5HHP Drive User Manual
Page 266

Advanced Operation
7.5.7 Operator Constants: o
7 - 102
D
Settings
Setting
Function
0
DATA/ENTER Key input required.
1
DATA/ENTER Key input not required.
Operation Selection when Digital Operator is Disconnected: o2-06
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
o2-06
Operation selection
when digital operator
is disconnected
x
0, 1
--
0
A
A
A
A
D
This constant specifies whether to stop operation when the Digital Operator is disconnected.
D
Settings
Setting
Function
0
Disable Operator detection. (Continue operation when the Digital Operator is disconnected.)
1
Enable Operator detection. (Detect an OPR fault when the Digital Operator is disconnected, stop
the Inverter output, and operate the fault contact.)
Cumulative Operation Time Settings: o2-07, o2-08
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
o2-07
Cumulative operation
time setting
x
0 to 65535
h
0
A
A
A
A
o2-08
Cumulative operation
time selection
x
0, 1
--
0
A
A
A
A
D
Set the initial elapsed time in constant o2-07. The elapsed operating time will start from this value.
D
Constant o2-08 determines whether the elapsed operating time is the time that the Inverter is on or the
time that the Inverter is running.
D
Settings
Setting
Function
0
Inverter power-on time. (Counts the elapsed time from start-up until power is turned off.)
1
Inverter running time. (Counts the elapsed time that there is an Inverter output.)
7