Multi-function output settings: h2 – Yaskawa G5HHP Drive User Manual
Page 240

Advanced Operation
7.5.5 External Terminal Functions: H
7 - 76
J
Multi-function Output Settings: H2
The settings and functions for the multi-function outputs are listed in Table 7.10.
Table 7.10 Multi-function Output Functions
Control Methods
Setting
value
Function
V/f
V/f
w/
PG
Open
loop
Vec-
tor
Flux
vec-
tor
0
During run ON: run command is ON or voltage is being output)
f
f
f
f
1
Zero-speed
f
f
f
f
2
Frequency agree 1: (Detection width L4-02)
f
f
f
f
3
Desired frequency agree 1 (ON: Output frequency = ±L4-01, detection width in L4-02)
f
f
f
f
4
Frequency (Four) detection 1 (ON: +L4-01≧output frequency≧--L4-01, detection width in L4-02)
f
f
f
f
5
Frequency (Four) detection 2
(ON: Output frequency≧+L4-01 or output frequency≦--L4-01, detection width in L4-02)
f
f
f
f
6
Inverter operation ready
READY: After initialization, no faults
f
f
f
f
7
During DC bus undervoltage (UV) detection
f
f
f
f
8
During baseblock (ON: during baseblock)
f
f
f
f
9
Frequency reference selection (ON: Frequency reference from Operator)
f
f
f
f
A
Run command selection (ON: Run command from Operator)
f
f
f
f
B
Overtorque detection 1 NO (NO contact: Overtorque detection at ON)
f
f
f
f
C
Loss of frequency reference (Effective when operation selection is “1” for L4-05 frequency reference missing)
f
f
f
f
D
Braking resistor fault (ON: Resistor overheat or braking transistor fault)
f
f
f
f
E
Fault (ON: Faults other than CPF00, CPF01 have occurred.)
f
f
f
f
F
Not used. (Do not set.)
--
--
--
--
10
Minor fault (ON: Alarm displayed)
f
f
f
f
11
Fault reset command active
f
f
f
f
12
Timer function output
f
f
f
f
13
Frequency agree 2 (Detection width: L4-04)
f
f
f
f
14
Desired frequency agree 2 (ON: Output frequency = L4-03, detection width in L4-04)
f
f
f
f
15
Frequency detection 3 (ON: Output frequency ≦--L4-03, detection width in L4-04)
f
f
f
f
16
Frequency detection 4 (ON: Output frequency ≧--L4-03, detection width in L4-04)
f
f
f
f
17
Overtorque detection 1 NC (NC Contact: Ttorque detection at OFF)
f
f
f
f
18
Overtorque detection 2 NO (NO Contact: Torque detection at ON)
f
f
f
f
19
Overtorque detection 2 NC (NC Contact: Torque detection at OFF)
f
f
f
f
1A
During reverse run (ON: During reverse run)
f
f
f
f
1B
During baseblock 2 (OFF: During baseblock)
f
f
f
f
1C
Motor selection (Motor under selection)
--
--
--
--
1D
Regenerating (ON: Regenerating)
f
1E
Restart enabled (ON: Restart enabled)
f
f
f
f
1F
Motor overload (OL1) pre-alarm (ON: 90% or more of the detection level)
f
f
f
f
20
Inverter overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 setting)
f
f
f
f
30
During torque limit (current limit) (ON: During torque limit)
x
x
f
f
31
During speed limit. (ON: During speed limit)
x
x
x
f
33
Zero-servo end (ON: Zero-servo function completed)
x
x
x
f
37
During run 2 (ON: Frequency output, OFF: Base block, DC injection braking, initial excitation, operation stop.
f
f
f
f
7