Analog outputs: h4 – Yaskawa G5HHP Drive User Manual
Page 297

8.2 Programming Mode Constants
8 - 31
J
Analog Outputs: H4
C
t t
Name
S tti
F t
Change
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
H4-01
Monitor selection
(terminal 45)
Sets the number of the monitor item
to be output (U1-
) from termi-
nal 21.
;
4 10 11 12 13 14 25 28 can
1 to 33
2
x
B
B
B
B
7 - 82
H4 01
Terminal 45 Sel
;
4, 10, 11, 12, 13, 14, 25, 28 can-
not be set and 29 to 31 are not
used.
1 to 33
2
x
B
B
B
B
7 - 82
H4-02
Gain (terminal 45)
Sets the multi-function analog out-
put 1 voltage level gain.
S ts h th r th monitor it m o t
0.00 to
1 00
f
B
B
B
B
7 82
H4-02
Terminal 45 Gain
Sets whether the monitor item out-
put will be output in multiples of 10
V.
0.00 to
2.50
1.00
f
B
B
B
B
7 - 82
H4-03
Bias (terminal 45)
Sets the multi-function analog out-
put 1 voltage level bias.
S ts o tp t ch r ct ristic p/do n
--10.0 to
0 0
f
B
B
B
B
7 82
H4-03
Terminal 45 Bias
Sets output characteristic up/down
parallel movement as a percentage
of 10 V.
--10.0 to
+10.0
0.0
f
B
B
B
B
7 - 82
H4-04
Monitor selection
(terminal 48)
Sets the number of the monitor item
to be output (U1-
) from termi-
nal 48.
;
4 10 11 12 13 14 25 28 can
1 to 33
3
x
B
B
B
B
7 - 82
H4 04
Terminal 48 Sel
;
4, 10, 11, 12, 13, 14, 25, 28 can-
not be set and 29 to 31 are not
used.
1 to 33
3
x
B
B
B
B
7 - 82
H4-05
Gain (terminal 48)
Sets the multi-function analog out-
put 2 voltage level gain.
S ts h th r th monitor it m o t
0.00 to
0 50
f
B
B
B
B
7 82
H4-05
Terminal 48 Gain
Sets whether the monitor item out-
put will be output in multiples of 10
V.
0.00 to
2.50
0.50
f
B
B
B
B
7 - 82
H4-06
Bias (terminal 48)
Sets the multi-function analog out-
put 2 voltage level bias.
S ts o tp t ch r ct ristic p/do n
--10.0 to
0 0
f
B
B
B
B
7 82
H4-06
Terminal 48 Bias
Sets output characteristic up/down
parallel movement as a percentage
of 10 V.
--10.0 to
+10.0
0.0
f
B
B
B
B
7 - 82
H4-07
Analog output signal
level selection
Sets the signal output level for mul-
ti-function outputs 1 and 2 (termi-
nals 45, 48.)
0: 0 to +10 V output
1: 0 to +10 V output
0 1
0
x
B
B
B
B
7 - 82
H4 07
AO Level Select
1: 0 to +10 V output
;
The optional Analog Monitor
Card may also be used with this
setting.
0 1
0
x
B
B
B
B
7 - 82
J
MEMOBUS Communications: H5
C
t t
Name
S tti
F t
Change
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
H5-01
Station address
Set the Inverter’s node address
0 to 20
1F
x
A
A
A
A
7 83
H5-01
Serial Comm Adr
Set the Inverter’s node address.
0 to 20
1F
x
A
A
A
A
7 - 83
H5-02
Communication
speed selection
Set the baud rate for 6CN MEMO-
BUS communications.
0: 1200 bps
1: 2400 bps
0 to 3
3
x
A
A
A
A
7 - 83
H5 02
Serial Com Sel
1: 2400 bps
2: 4800 bps
3: 9600 bps
0 to 3
3
x
A
A
A
A
7 - 83
8