Yaskawa G5HHP Drive User Manual
Page 194

Advanced Operation
7.3.6 Setting/Adjusting Motor Constants
7 - 30
Frequency (Hz)
Output voltage (V)
VMAX
(E1-05)
FMIN
(E1-09)
FA
(E1-06)
FMAX
(E1-04)
V BASE
(E1-13)
Fig 7.16
V/f Pattern Adjustment
Units for V/f Pattern Settings: o1-04
The units used for V/f pattern frequency settings can be changed when flux vector control has been selected.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
o1-04
Frequency units of
constant setting
x
0, 1
--
0
x
x
x
B
D
Display Unit Settings
Setting
Function
0
Units: Hz
1
Units: r/min
D
The setting units for constants E1-04, E1-06, and E1-09 can be changed.
D
The unit for other frequencies will not change.
D
Constant o1-04 is specific to flux vector control.
J
Setting Motor Constants: E2-01 to E2-09
The motor constants (function E2) will all be set automatically when autotuning is performed.
Set these constants manually if autotuning can’t be completed properly.
Motor Rated Current: E2-01
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
E2-01
Motor rated current
x
37.0 to
740.0
A
370
Q
Q
Q
Q
D
The setting range is 10% to 200% of the Inverter rated output current. The default setting depends upon
the Inverter capacity. (The table shows the default setting for 400-V class, 200 kW Inverters.) See page
8 - 42.)
D
Set the rated current (A) shown on the motor nameplate.
Motor Rated Slip: E2-02
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
E2-02
Motor rated slip
x
0.00 to
20.00
Hz
1.3
A
A
Q
Q
D
The default setting depends upon the Inverter capacity.
(The table shows the default settings for 400-V class, 200 kW Inverters.) (See page 8 - 42.)
D
Calculate the rated slip (E2-02) from the value shown on the motor nameplate with the following equa-
tion and set this value.
Rated slip = rated frequency (Hz) -- rated speed (r/min) × number of poles/120
7