Frequency reference source: b1-01 – Yaskawa G5HHP Drive User Manual
Page 125

6.1 Common Settings
6 - 7
Analog Input Filter Time Constant: H3-12
D
A primary delay digital filter can be set for all three analog inputs (frequency reference (voltage), fre-
quency reference (current), and multi-function analog input)
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
H3-12
Analog input filter
time constant
x
0.00 to 2.00
s
0.00
A
A
A
A
D
This setting is effective when there are sudden changes or noise in the analog input signal.
D
Responsiveness decreases as the setting increases.
6.1.3 Frequency Reference from Digital Operator: b1-01, o1-03, d1-01 to d1-09
J
Frequency Reference Source: b1-01
D
Select the reference source.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
b1-01
Reference selection
x
0 to 3
--
1
Q
Q
Q
Q
D
Settings
Setting
Reference source
0
Digital Operator
1
Control circuit terminals (analog inputs)
2
Transmission
3
Optional Card
D
The frequency reference is input from the Digital Operator, so set b1-01 to 0.
J
Frequency Unit for Reference Setting and Monitoring: o1-03
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
o1-03
Frequency unit for
reference setting and
monitor
x
0 to 39999
--
0
B
B
B
B
D
Settings
Setting
Function
0
0.01 Hz units
1
0.01% units (The maximum frequency is 100%.)
2 to 39
r/min units (Set the number of poles.)
r/min = 120 X frequency reference (Hz)/o1--03
(o1--03 sets the motor poles.)
40 to 39999
Decimal point is set according to the 5th digit value of o1--03.
5th digit = 0: Displays
5th digit = 1: Displays
.
5th digit = 2: Displays
.
5th digit = 3: Displays .
Setting values of 100% frequency are set according to the first to fourth digits of o1--03
[Example 1]
When the setting value (100% speed) is 200.0, o1--03 is set to 12000.
When o1--03 is set to 12000, 100% speed displays 200.0. 60% speed displays 120.0.
[Example 2]
When the setting value (100% speed) is 65.00, o1--03 is set to 26500.
When o1--03 is set to 26500, 60% speed displays 39.00.
6