6.1 Common Settings

6 - 11

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

C1-09

Emergency stop time

f

0.0 to

6000.0

s

10.0

B

B

B

B

D

The setting range for the emergency stop deceleration time depends upon the setting in C1-10 (accelera-

tion/deceleration time unit). The table shows the setting range when the factory setting is used for C1-10.

D

If C1-10 is set to “0” (0.01 s) the setting range will be 0.00 to 600.00 s.

J

Acceleration/Deceleration Time Switching Frequency: C1-11

D

When an acceleration/deceleration time switching frequency is set, the acceleration and deceleration

times will be changed automatically as the frequency passes the set level.

D

If the acceleration/deceleration time selectors 1 and 2 are input via the multi-function inputs, they will

have priority.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

C1-11

Accel/decel time

switching frequency

x

0.0 to 150.0

Hz

0.0

A

A

A

A

Acceleration/Deceleration Times 1 (C1-01 and C1-02) are used when the output frequency ≥ C1-11

Acceleration/Deceleration Times 4 (C1-07 and C1-08) are used when the output frequency < C1-11

Output frequency

Acc/Dec Time Switch-

ing Frequency (C1-11)

C1-07

C1-02

C1-01

C1-08

Fig 6.3

Acceleration/Deceleration Time Switching Frequency

6.1.6 Prohibiting Reverse Operation: b1-04

D

Set whether or not to operate the motor in reverse when a reverse reference is input.

D

Set this constant to “1” to disable reverse operation when necessary.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

b1-04

Prohibition of reverse

operation

x

0, 1

--

0

B

B

B

B

D

Settings

Setting

Function

0

Allows reverse operation.

1

Prohibits reverse operation.

6