Yaskawa G5HHP Drive User Manual
Page 307

8.2 Programming Mode Constants
8 - 41
8.2.9 Factory Settings that Change with the Control Method (A1-02)
Name
Factory Setting
Con-
stant
No.
Display
Setting
Range
Unit
V/f Con-
trol
A1-02=0
V/f with
PG
A1-02=1
Open
Loop
Vector
A1-02=2
Flux Vec-
tor
A1-02=3
b3-01
Speed search selection at start
0 1
1
0
1
0
1
b3-01
SpfSrch at Start
0 1
1
0
1
0
1
b3-02
Speed search operating current
0 to 200
1%
150
100
b3-02
SpdSrch Current
0 to 200
1%
150
----
100
----
C3-01
Slip compensation gain
0 0 to 2 5
0 1
0 0
1 0
1 0
C3-01
Slip Comp gain
0.0 to 2.5
0.1
0.0
----
1.0
1.0
C3-02
Slip compensation primary delay time
0 to 10000
1 msec
2000
200
C3-02
Slip Comp Time
0 to 10000
1 msec
2000
----
200
----
C4-02
Torque compensation time constant
0 to 10000
1 msec
200
200
20
C4-02
Torq Comp Time
0 to 10000
1 msec
200
200
20
----
C5-01
ASR proportional (P) gain 1
0 00 to 300 00
0 01
0 20
20 00
C5-01
ASR P Gain 1
0.00 to 300.00
0.01
----
0.20
----
20.00
C5-02
ASR integral (I) time 1
0.000 to
0 001 sec
0 200
0 500
C5-02
ASR I Time 1
0.000 to
10.000
0.001 sec
----
0.200
----
0.500
C5-03
ASR proportional (P) gain 2
0 00 to 300 00
0 01
0 02
20 00
C5-03
ASR P Gain 2
0.00 to 300.00
0.01
----
0.02
----
20.00
C5-04
ASR integral (I) time 2
0.000 to
0 001 sec
0 050
0 500
C5-04
ASR I Time 2
0.000 to
10.000
0.001 sec
----
0.050
----
0.500
E1-07 Mid. output frequency
0 0 to 150 0
0 1 Hz
3 0
3 0
3 0
0 0
E1 07
E4-04 Mid Frequency A
0.0 to 150.0
0.1 Hz
3.0
3.0
3.0
0.0
E1-08 Mid. output frequency voltage
0.0 to 510.0
0 1 V
*
*
22.0
0 0
E1 08
E4-05 Mid voltage A
0.0 to 510.0
(0.0 to 733.0)
0.1 V
*
*
22.0
(31.6)
0.0
E1-09 Min. output frequency
0 0 to 150 0
0 1 Hz
1 5
1 5
0 5
0 0
E1 09
E4-06 Min Frequency
0.0 to 150.0
0.1 Hz
1.5
1.5
0.5
0.0
E1-10 Min. output frequency voltage
0.0 to 510.0
0 1 V
*
*
4.0
0 0
E1 10
E4-07 Min Voltage
0.0 to 510.0
(0.0 to 733.0)
0.1 V
*
*
4.0
(5.8)
0.0
F1-09
Overspeed detection delay time
0 0 to 2 0
0 1 sec
1 0
0 0
F1-09
PG Overspd Time
0.0 to 2.0
0.1 sec
----
1.0
----
0.0
Note Values in parentheses are for 575-V class Inverters.
* Settings vary as shown in the following tables depending on the Inverter capacity.
400-V Class Inverters
Inverter Capacity (kW)
200 to 800
E1-08, E4-05
24.0
E1-10, E4-06
12.0
575-V Class Inverters
Inverter Capacity (kW)
300 to 1200
E1-08, E4-05
34.5
E1-10, E4-06
17.3
8