Basic Operation
6.1.3 Frequency Reference from Digital Operator: b1-01, o1-03, d1-01 to d1-09
6 - 8
D
When the 40 to 39,999 range is used, any unit can be set for the reference frequency.
For example, the frequency reference can be displayed or set in units such as mm/s or m/min to coincide
with the linear operating speed of the machine.
J
Preset Frequency Reference Values: d1-01 through d1-09
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
d1-01
Frequency reference
1
f
0 to 150.00
o1-03 0.00 Hz
Q
Q
Q
Q
d1-02
Frequency reference
2
f
0 to 150.00
o1-03 0.00 Hz
Q
Q
Q
Q
d1-03
Frequency reference
3
f
0 to 150.00
o1-03 0.00 Hz
Q
Q
Q
Q
d1-04
Frequency reference
4
f
0 to 150.00
o1-03 0.00 Hz
Q
Q
Q
Q
d1-05
Frequency reference
5
f
0 to 150.00
o1-03 0.00 Hz
B
B
B
B
d1-06
Frequency reference
6
f
0 to 150.00
o1-03 0.00 Hz
B
B
B
B
d1-07
Frequency reference
7
f
0 to 150.00
o1-03 0.00 Hz
B
B
B
B
d1-08
Frequency reference
8
f
0 to 150.00
o1-03 0.00 Hz
B
B
B
B
d1-09
Jog frequency refer-
ence
f
0 to 150.00
o1-03 6.00 Hz
Q
Q
Q
Q
D
The units for these values are set in o1-03.
D
The frequency reference default value and set value will change when o1-03 is changed.
For example, if preset reference 1 is set to 6.00 Hz and o1-03 is changed to 1 (0.01% units), the setting
for preset reference 1 will become 10.00%.
D
When using preset references 2 through 8, be sure to set multi-step speed references 1, 2, and 3 in the
multi-function inputs (H1-01 through H1-06) as required.
D
When using the jog function, set the jog frequency reference in constant d1-09. When jogging from an
external terminal, set the multi-function inputs (H1-01 through H1-06) to “Jog Frequency Reference,”
“Forward Jog,” or “Reverse Jog” as required.
D
The multi-function input setting is unnecessary when jogging from the Operator.
6