beautypg.com

2 autotuning faults, Performing autotuning – Yaskawa G5HHP Drive User Manual

Page 137

background image

6.2 Open-loop Vector Control

6 - 19

3. At this point, it is still possible to change the constant settings by pressing the Increment and Decrement

Keys to display the desired constant.

4. Press the STOP Key to cancel autotuning, and then press the MENU Key and DATA/ENTER Key. The

operation mode display will appear.

* Rated voltage forvectorcontrol motors is approx. 10 to 20% lowerthan general--purpose mo-

tors. Always verify motor voltage listed on the nameplate or test report before use.

J

Performing Autotuning

D

Autotuning will start if the RUN Key is pressed when the “Tuning Ready?” message is being displayed.

D

The motor will operate during autotuning, so be sure that it is safe for the motor to operate before press-

ing the RUN Key.

D

The following message will be displayed when the RUN Key is pressed:

Tune Proceeding

Hz

A

The “Tune Proceeding” message will blink.

D

Autotuning takes up to 1.5 minutes. The message“Tune Successful” will be displayed when autotuning

has been completed.

D

If autotuning has been completed successfully, press the MENU Key and proceed to the next operation.

D

If a fault occurred during autotuning, refer to 6.2.2 Autotuning Faults for details on correcting the cause

of the fault and perform autotuning again.

6.2.2 Autotuning Faults

D

One of the fault messages in the following table will be displayed if a fault occurs during autotuning

and the motor will stop. In this case, determine the cause of the fault, correct it, and perform autotuning

again.

D

The fault display can be cleared by pressing the MENU Key.

D

The motor constants will revert to their default settings if a fault occurs. Set these constants again before

starting autotuning again.

Table 6.2 Troubleshooting Autotuning Faults for Open-loop Vector Control

Fault Display

Probable Cause

Remedy

Data Invalid
(Motor data fault)

There was a fault in the data

set during autotuning.

There was a fault in the rela-

tionship between the rated

frequency, rated speed, and

number of poles.

Change the settings to conform to the follow-

ing equation:

Rated speed < 120 × Motor frequency/Num-

ber of poles

A load is connected to the

motor.

Remove the load.

ALARM: Over Load
(Excessive tuning load)

The effective load factor ex-

ceeded 20% during autotun-

ing

There was a setting fault dur-

ing autotuning.

Check the rated current setting. Change if

necessary.

(Excessive tuning load)

ing.

There is a motor bearing

problem.

Turn the Inverter off and rotate the motor by

hand.

Replace the motor if it doesn’t turn smoothly.

Motor speed

The torque reference value

exceeded 100% during auto

There is a broken/discon-

nected motor power wire.

Check and replace wiring components if nec-

essary.

Motor speed
(Motor speed fault)

exceeded 100% during auto-

tuning.

A load is connected to the

motor.

Remove the load.

The torque limit function is

operating.

Initialize the torque limit constants (H7-01 to

H7-04).

Accelerate
(Acceleration fault)

The motor doesn’t accelerate

within the prescribed time.

The acceleration time is too

short.

Increase acceleration time 1 (C1-01).

(Acceleration fault)

A load is connected to the

motor.

Remove the load.

Rated Slip
(Rated slip fault)

The rated slip setting can’t be

tuned within the prescribed

time.

A load is connected to the

motor.

Remove the load.

6