4 flux vector control, 1 pg speed control card settings, Available pg speed control cards – Yaskawa G5HHP Drive User Manual
Page 144: Pg constant: f1-01, Pg rotation direction: f1-05

Basic Operation
6.4.1 PG Speed Control Card Settings
6 - 26
6.4 Flux Vector Control
With flux vector control (vector control with PG), make the settings for the PG Speed Control Card, select the
zero-speed operation method, set the various autotuning constants, and then adjust the gain of the speed control
loop.
Always perform auto--tuning for motor unit separately before vector control operation. Vector control is not ef-
fective without autotuning.
To ensure high-accuracy torque/speed control, use a motor specifically designed for vector control with an inte-
grated PG.
When setting up a PG (encoder), connect it directly to the motor shaft. If the PG is connected to the motor via
gearing or belts, responses can be delayed by backlash or torsion; the delayed responses can generate oscillation
and make control impossible.
6.4.1 PG Speed Control Card Settings
J
Available PG Speed Control Cards
D
There are 4 models of PG Speed Control Cards, but only 2 models can be used with vector control.
•
PG-B2: Phase-A/Phase-B pulse inputs, complementary output
•
PG-X2: Phase-A/Phase-B/Phase-Z pulse inputs, line drivers
D
Select the Card according to the application and install it in the Inverter as described in 3.7 Installing
and Wiring PG Speed Control Cards.
J
PG Constant: F1-01
D
Set the PG (pulse generator or encoder) constant in pulses/revolution.
D
Set the number of phase-A or phase-B pulses in one motor revolution.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
F1-01
PG constant
x
0 to 60000
p/r
600
x
Q
x
Q
J
PG Rotation Direction: F1-05
D
This constant is used to coordinate the PG’s rotation direction with the motor’s rotation direction.
The setting for the standard applicable Yaskawa PG (made by Thermtac) is an advanced phase A for
forward rotation.
D
Generally, phase A leads when the PG rotates in the clockwise direction (looking from the input axis).
When a forward reference is output, the motor rotates in the counterclockwise direction (looking from
the output axis).
D
Set whether phase A or phase B leads when the motor operates in the forward direction.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
F1-05
PG rotation
x
0, 1
--
0
x
B
x
B
D
Settings
Setting
Function
0
Phase A leads with forward rotation. (Phase B leads with reverse rotation.)
1
Phase B leads with forward rotation. (Phase A leads with reverse rotation.)
6