2 mounting, 1 optional rear-mounting support brackets – Comtech EF Data CDM-600/600L User Manual
Page 58

CDM-600/600L Open Network Satellite Modem
Revision 3
Installation
MN/CDM600L.IOM
2–2
2.2
Mounting
If the CDM-600/600L is to be mounted in a rack, ensure that there is adequate clearance for
ventilation, particularly at the sides. In rack systems where there is high heat dissipation, forced
air cooling must be provided by top or bottom mounted fans or blowers. Under no circumstance
should the highest internal rack temperature be allowed to exceed 50°C (122°F).
IMPORTANT
The CDM-600/600L
CANNOT
have rack slides mounted to the side of the chassis.
Two cooling fans are installed in the right-hand side of the unit. Comtech EF Data
therefore recommends that an alternate method of support, such as rack shelves, is
employed within the rack. If there is any doubt, please consult the Comtech EF Data
Customer Support department.
2.2.1 Optional Rear-Mounting Support Brackets
Install optional rear-mounting support brackets using mounting kit KT/6228-2:
Quantity
Part Number
Description
2
HW/10-32SHLDR
Screw, #10 Shoulder
4 HW/10-32FLT
Washer,
#10
Flat
2 HW/10-32SPLIT Washer,
#10
Split
2
HW/10-32HEXNUT
Nut, #10 Hex
2
FP/6138-1
Bracket, Rear Support
4
HW/10-32x1/2RK
Bolt, #10 Rack Bracket
The tools required for this installation are a medium Phillips
™ screwdriver and a 5/32-inch
SAE Allen
™ Wrench. The kit is installed as illustrated in Figure 2-1 via the following
procedure:
Step
Procedure
1
Secure the #10 shoulder screws to the unit chassis through the rear right and left
side mounting slots, using the #10 flat washers, #10 split washers, and #10 hex
nuts as shown.
2
Install the rear support brackets onto the equipment rack threaded rear mounting
rails, using the #10 rack bracket bolts.
3
Mount the unit into the equipment rack, ensuring that the shoulders of the #10
shoulder screws properly engage into the rear support bracket slots.