2 mounting, 1 optional rear-mounting support brackets – Comtech EF Data CDM-600/600L User Manual

Page 58

background image

CDM-600/600L Open Network Satellite Modem

Revision 3

Installation

MN/CDM600L.IOM

2–2

2.2

Mounting

If the CDM-600/600L is to be mounted in a rack, ensure that there is adequate clearance for
ventilation, particularly at the sides. In rack systems where there is high heat dissipation, forced
air cooling must be provided by top or bottom mounted fans or blowers. Under no circumstance
should the highest internal rack temperature be allowed to exceed 50°C (122°F).

IMPORTANT

The CDM-600/600L

CANNOT

have rack slides mounted to the side of the chassis.

Two cooling fans are installed in the right-hand side of the unit. Comtech EF Data
therefore recommends that an alternate method of support, such as rack shelves, is
employed within the rack. If there is any doubt, please consult the Comtech EF Data
Customer Support department.

2.2.1 Optional Rear-Mounting Support Brackets

Install optional rear-mounting support brackets using mounting kit KT/6228-2:

Quantity

Part Number

Description

2

HW/10-32SHLDR

Screw, #10 Shoulder

4 HW/10-32FLT

Washer,

#10

Flat

2 HW/10-32SPLIT Washer,

#10

Split

2

HW/10-32HEXNUT

Nut, #10 Hex

2

FP/6138-1

Bracket, Rear Support

4

HW/10-32x1/2RK

Bolt, #10 Rack Bracket

The tools required for this installation are a medium Phillips

screwdriver and a 5/32-inch

SAE Allen

Wrench. The kit is installed as illustrated in Figure 2-1 via the following

procedure:

Step

Procedure

1

Secure the #10 shoulder screws to the unit chassis through the rear right and left
side mounting slots, using the #10 flat washers, #10 split washers, and #10 hex
nuts as shown.

2

Install the rear support brackets onto the equipment rack threaded rear mounting
rails, using the #10 rack bracket bolts.

3

Mount the unit into the equipment rack, ensuring that the shoulders of the #10
shoulder screws properly engage into the rear support bracket slots.