DGC-2020HD Modbus

™ Protocol

Default Register Table

Name

Description

Group Register Type Bytes R/W

Unit

Range

AEM 3 TC Input 2=353
AEM 4 Analog Input 1=354

AEM 4 Analog Input 2=355

AEM 4 Analog Input 3=356
AEM 4 Analog Input 4=357

AEM 4 Analog Input 5=358
AEM 4 Analog Input 6=359

AEM 4 Analog Input 7=360
AEM 4 Analog Input 8=361

AEM 4 RTD Input 1=362

AEM 4 RTD Input 2=363
AEM 4 RTD Input 3=364

AEM 4 RTD Input 4=365
AEM 4 RTD Input 5=366

AEM 4 RTD Input 6=367
AEM 4 RTD Input 7=368

AEM 4 RTD Input 8=369

AEM 4 TC Input 1=370
AEM 4 TC Input 2=371

AVR Output=372
GOV Output=373

LS Output=374

AEM 1 Remote Analog

Output 2

Out-of-Range Activation

Delay

GG

7356

Float

4

R W Second 0 - 300

AEM 1 Remote Analog

Output 2

Param Minimum

GG

7358

Float

4

R W n/a

-999999 - 999999

AEM 1 Remote Analog
Output 2

Param Maximum

GG

7360

Float

4

R W n/a

-999999 - 999999

AEM 1 Remote Analog
Output 2

Current Minimum

GG

7362

Float

4

R W Milliamp 4 - 20

AEM 1 Remote Analog
Output 2

Current Maximum

GG

7364

Float

4

R W Milliamp 4 - 20

AEM 1 Remote Analog
Output 2

Voltage Minimum

GG

7366

Float

4

R W Volt

0 - 10

AEM 1 Remote Analog

Output 2

Voltage Maximum

GG

7368

Float

4

R W Volt

0 - 10

AEM 1 Remote Analog

Output 2

Alarm Configuration

GG

7370

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

AEM 1 Remote Analog
Output 3

Parameter Selection

GG

7372

Int32

4

R W n/a

No Parameter=0
Oil Pressure=1

Coolant Temp=2
Battery Volts=3

RPM=4

Fuel Level=5
Gen Hz=6

Gen VAB=7
Gen VBC=8

Gen VCA=9
Gen Vavg LL=10

Gen VAN=11

Gen VBN=12
Gen VCN=13

Gen Vavg LN=14
Bus 1 Hz=15

Bus 1 VAB=16
Bus 1 VBC=17

Bus 1 VCA=18

Bus 1 Vavg LL=19
Bus 1 VA=20

Bus 1 VB=21
Bus 1 VC=22

Bus 1 Vavg LN=23
Bus 2 Hz=24

Bus 2 VAB=25
Bus 2 VBC=26

Bus 2 VCA=27

Bus 2 Vavg LL=28
Bus 2 VAN=29

Bus 2 VBN=30
Bus 2 VCN=31

Bus 2 Vavg LN=32
Gen PF=33

Bus 1 PF=34

Bus 2 PF=35
Gen Pos kWh=36

Gen Neg kWh=37
Bus 1 Pos kWh=38

Bus 1 Neg kWh=39
Bus 2 Pos kWh=40

Bus 2 Neg kWh=41