Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 251
![background image](https://www.manualsdir.com/files/773959/content/doc251.png)
9469300991 Rev A
245
DGC-2020HD Modbus
™ Protocol
Legacy Register Table
Register
Description
Type
Units
Scaling
Factor
R/W
Range
44754
Gen VCA Metering
Int32
Volt
n/a
R
(-2147483648) - 2147483647
44756
Gen VAN Metering
Int32
Volt
n/a
R
(-2147483648) - 2147483647
44758
Gen VBN Metering
Int32
Volt
n/a
R
(-2147483648) - 2147483647
44760
Gen VCN Metering
Int32
Volt
n/a
R
(-2147483648) - 2147483647
44762
Bus Voltage Metering
Int32
Volt
n/a
R
(-2147483648) - 2147483647
44764
Gen IA Metering
Int32
Amp
n/a
R
(-32768) - 32767
44766
Gen IB Metering
Int32
Amp
n/a
R
(-32768) - 32767
44768
Gen IC Metering
Int32
Amp
n/a
R
(-32768) - 32767
44770
Gen kVA A Metering
Int32
kiloVA
n/a
R
(-2147483648) - 2147483647
44772
Gen kVA B Metering
Int32
kiloVA
n/a
R
(-2147483648) - 2147483647
44774
Gen kVA C Metering
Int32
kiloVA
n/a
R
(-2147483648) - 2147483647
44776
Gen kVA Total Metering
Int32
kiloVA
n/a
R
(-2147483648) - 2147483647
44778
Gen kW A Metering
Int32
kilowatt
n/a
R
(-2147483648) - 2147483647
44780
Gen kW B Metering
Int32
kilowatt
n/a
R
(-2147483648) - 2147483647
44782
Gen kW C Metering
Int32
kilowatt
n/a
R
(-2147483648) - 2147483647
44784
Gen kW Total Metering
Int32
kilowatt
n/a
R
(-2147483648) - 2147483647
44786
Power Factor Metering
Float
n/a
n/a
R
(-1) - 1
44788
Gen PF Lagging
Int32
n/a
n/a
R
(-128) - 127
44790
Gen Frequency Metering
Float
Hertz
n/a
R
45 - 440
44792
Bus Frequency Metering
Float
Hertz
n/a
R
45 - 440
44794
Active Speed Source
Uint32 n/a
n/a
R
1 = Magnetic Pickup
2 = Gen Freq
3 = MPU/Gen Freq
44796
Engine Speed Metering
Uint32 RPM
n/a
R
0 - 65535
44798
Engine Load Metering
Int32
Percent
n/a
R
(-32768) - 32767
44800
Coolant Temp. Metering
Int32
Deg F
n/a
R
(-32768) - 32767
44802
Oil Pressure Metering
Int32
PSI
n/a
R
(-32768) - 32767
44804
Battery Voltage Metering
Int32
DeciVolt
n/a
R
(-32768) - 32767
44806
Fuel Level Metering
Int32
n/a
n/a
R
(-32768) - 32767
44808
ECU Coolant Level Metering
Uint32 n/a
n/a
R
0 - 255
44810
Cool Down Time Remaining
Int32
Minute
n/a
R
(-128) - 127
44812-13
Alarm Metering
Int32
n/a
n/a
R
Bit 0 = Not Used
Bit 1 = Not Used
Bit 2 = Not Used
Bit 3 = Not Used
Bit 4 = Not Used
Bit 5 = Not Used
Bit 6 = Not Used
Bit 7 = Not Used
Bit 8 = Not Used
Bit 9 = Not Used
Bit 10 = Not Used
Bit 11 = Not Used
Bit 12 = Not Used
Bit 13 = Not Used
Bit 14 = Not Used
Bit 15 = Not Used
Bit 16 = Unexpected Shutdown
Bit 17 = Global Alarm
Bit 18 = Auto Restart Failure
Bit 19 = Fuel Leak Detect
Bit 20 = Battery Charger Failure
Bit 21 = Transfer Fail
Bit 22 = Low Coolant Level
Bit 23 = ECU Shutdown
Bit 24 = Emergency Shutdown
Bit 25 = Overcrank
Bit 26 = Loss of ECU Comms
Bit 27 = Global Sender Fail
Bit 28 = Low Fuel Level
Bit 29 = Low Oil Pressure
Bit 30 = Hi Coolant Temp
Bit 31 = Overspeed