Senders – Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 240
![background image](https://www.manualsdir.com/files/773959/content/doc240.png)
234
9469300991 Rev A
Legacy Register Table
DGC-2020HD Modbus
™ Protocol
Register
Description
Type
Units
Scaling Factor
R/W
Range
42784
Bus Sensing Stable Undervoltage Pickup
Int32
Volt
n/a
RW
10 - 9999
42786
Bus Sensing Stable Undervoltage Dropout
Int32
Volt
n/a
RW
10 - 9999
42788
Bus Sensing Stable Overvoltage Pickup
Int32
Volt
n/a
RW
10 - 9999
42790
Bus Sensing Stable Overvoltage Dropout
Int32
Volt
n/a
RW
10 - 9999
42792
Bus Sensing Stable Underfrequency Pickup
Int32
CentiHertz
Centi
RW
4600 - 6400
42794
Bus Sensing Stable Underfrequency Dropout
Int32
CentiHertz
Centi
RW
4600 - 6400
42796
Bus Sensing Stable Overfrequency Pickup
Int32
CentiHertz
Centi
RW
4600 - 6400
42798
Bus Sensing Stable Overfrequency Dropout
Int32
CentiHertz
Centi
RW
4600 - 6400
42800
Bus Sensing Fail Time Delay
Int32
Decisecond
Deci
RW
1 - 6000
42802
Bus Sensing Stable Time Delay
Int32
Decisecond
Deci
RW
1 - 6000
42804
Reserved
42806
Gen Dead Status
Int32
n/a
n/a
R
0 - 1
42808
Gen Stable Status
Int32
n/a
n/a
R
0 - 1
42810
Gen Fail Status
Int32
n/a
n/a
R
0 - 1
42812
Bus Dead Status
Int32
n/a
n/a
R
0 - 1
42814
Bus Stable Status
Int32
n/a
n/a
R
0 - 1
42816
Bus Fail Status
Int32
n/a
n/a
R
0 - 1
42818
Gen Stable Low Line Scale Factor
Float
n/a
n/a
RW
0.001 - 3
42820
Bus Stable Low Line Scale Factor
Float
n/a
n/a
RW
0.001 - 3
42822
Gen Stable Alternate Frequency Scale Factor
Float
n/a
n/a
RW
0.001 - 100
42824
Bus Stable Alternate Frequency Scale Factor
Float
n/a
n/a
RW
0.001 - 100
Senders
Register
Description
Type
Units
Scaling Factor R/W
Range
43434
Coolant Temperature Sender Fail Configuration Type
Int32 n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
43436
Coolant Temperature Sender Fail Activation Delay
Int32 Minute
n/a
RW
5 - 30
43438
Oil Pressure Sender Fail Configuration Type
Int32 n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
43440
Oil Pressure Sender Fail Activation Delay
Int32 Second n/a
RW
0 - 300
43442
Fuel Level Sender Fail Configuration Type
Int32 n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
43444
Fuel Level Sender Fail Activation Delay
Int32 Second n/a
RW
0 - 300
43446
Voltage Sensing Fail Configuration Type
Int32 n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
43448
Voltage Sensing Fail Activation Delay
Int32 Second n/a
RW
0 - 300
43450
Low Coolant Level Contact Input
Int32 n/a
n/a
RW
-1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16
43452
Low Coolant Level Config Type
Int32 n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
43454
Low Coolant Level Time Delay
Int32 Second n/a
RW
0 - 300