Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 203
9469300991 Rev A
197
DGC-2020HD Modbus
™ Protocol
Default Register Table
Name
Description
Group Register Type Bytes R/W
Unit
Range
51-5
Mode
SG3 3P 24284
Uint32 4
R W n/a
Disabled=0
IA=1
IB=2
IC=3
Imax=4
3I0=5
I2=6
IG=7
I1=8
51-5
Source
SG3 3P 24286
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-5
Pickup
SG3 3P 24288
Float
4
R W Amp
0.9 - 7.75
51-5
Curve Index
SG3 3P 24290
Uint32 4
R W n/a
S1=0
S2=1
L1=2
L2=3
D=4
M=5
I1=6
I2=7
V1=8
V2=9
E1=10
E2=11
A=12
B=13
C=14
G=15
F=16
46=17
P=18
51-5
Direction
SG3 3P 24292
Uint32 4
R W n/a
Forward=0
Reverse=1
Non-Directional=2
51-5
Use Instantaneous Reset
SG3 3P 24294
Uint32 4
R W n/a
Integrating=0
Instantaneous=1
51-5
Constant TD
SG3 3P 24296
Float
4
R W n/a
0 - 9.9
51-5
Constant A
SG3 3P 24298
Float
4
R W n/a
0 - 600
51-5
Constant B
SG3 3P 24300
Float
4
R W n/a
0 - 25
51-5
Constant C
SG3 3P 24302
Float
4
R W n/a
0 - 1
51-5
Constant N
SG3 3P 24304
Float
4
R W n/a
0.5 - 2.5
51-5
Constant R
SG3 3P 24306
Float
4
R W n/a
0 - 30
51-5
Voltage Restraint Setpoint
SG3 3P 24308
Float
4
R W Volt
30 - 250
51-5
Voltage Restraint Mode
SG3 3P 24310
Uint32 4
R W n/a
Disabled=0
Control=1
Restraint=2
51-5
Alarm Configuration
SG3 3P 24312
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
51-5
Low-Line Scale
SG3 3P 24314
Float
4
R W n/a
0.001 - 3
51-5
Voltage Restraint Source
SG3 3P 24316
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-5
Constant Q
SG3 3P 24318
Float
4
R W n/a
0.1 - 10
51-6
Mode
SG0 1P 24320
Uint32 4
R W n/a
Disabled=0
IA=1
IB=2
IC=3
Imax=4
3I0=5
I2=6
IG=7
I1=8
51-6
Source
SG0 1P 24322
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-6
Pickup
SG0 1P 24324
Float
4
R W Amp
0.9 - 7.75