Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group
Register
Type
Bytes R/W
Unit
Range
Bias Control
PF Setpoint Source
GG
2128
Uint32
4
R W n/a
User Setting=0
Local Analog Input 1=1
Local Analog Input 2=2
Local Analog Input 3=3
Local Analog Input 4=4
AEM 1 Analog Input 1=5
AEM 1 Analog Input 2=6
AEM 1 Analog Input 3=7
AEM 1 Analog Input 4=8
AEM 1 Analog Input 5=9
AEM 1 Analog Input 6=10
AEM 1 Analog Input 7=11
AEM 1 Analog Input 8=12
AEM 2 Analog Input 1=13
AEM 2 Analog Input 2=14
AEM 2 Analog Input 3=15
AEM 2 Analog Input 4=16
AEM 2 Analog Input 5=17
AEM 2 Analog Input 6=18
AEM 2 Analog Input 7=19
AEM 2 Analog Input 8=20
AEM 3 Analog Input 1=21
AEM 3 Analog Input 2=22
AEM 3 Analog Input 3=23
AEM 3 Analog Input 4=24
AEM 3 Analog Input 5=25
AEM 3 Analog Input 6=26
AEM 3 Analog Input 7=27
AEM 3 Analog Input 8=28
AEM 4 Analog Input 1=29
AEM 4 Analog Input 2=30
AEM 4 Analog Input 3=31
AEM 4 Analog Input 4=32
AEM 4 Analog Input 5=33
AEM 4 Analog Input 6=34
AEM 4 Analog Input 7=35
AEM 4 Analog Input 8=36
Bias Control
Base Load Analog Max
GG
2130
Float
4
R W Percent
0 - 100
Bias Control
Base Load Analog Min
GG
2132
Float
4
R W Percent
0 - 100
Bias Control
kvar Analog Max
GG
2134
Float
4
R W Percent
-100 - 100
Bias Control
kvar Analog Min
GG
2136
Float
4
R W Percent
-100 - 100
Bias Control
PF Analog Max
GG
2138
Uint32
4
R W n/a
160 - 240
Bias Control
PF Analog Min
GG
2140
Uint32
4
R W n/a
160 - 240
Bias Control
var Droop Percentage
GG
2142
Float
4
R W Percent
0.5 - 10
Bias Control
Base Load Level
GG
2144
Float
4
R W Percent
0 - 100
Bias Control
kvar Setpoint
GG
2146
Float
4
R W Percent
-100 - 100
Bias Control
PF Setpoint
GG
2148
Uint32
4
R W n/a
160 - 240
Bias Control
var Control Mode
GG
2150
Uint32
4
R W n/a
var Control=0
PF Control=1
Bias Control
Load Share Interface
GG
2152
Uint32
4
R W n/a
Load Share Line=0
Ethernet Comms=1