Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 280

274
9469300991 Rev A
Legacy Register Table
DGC-2020HD Modbus
™ Protocol
Register
Description
Type
Units
Scaling
Factor
R/W
Range
45816
Conf Prot 2 Over 2 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
45818
Conf Prot 2 Under 1 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
45820
Conf Prot 2 Under 2 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
45822
Conf Prot 3 Param Select
Uint32 n/a
n/a
RW No Parameter=0
OIL P=1
Coolant Temp=2
BATT V=3
RPM=4
FUEL LVL=5
Gen Hz=6
Gen VAB=7
Gen VBC=8
Gen VCA=9
Gen Vavg LL=10
GEN VAN=11
GEN VBN=12
GEN VCN=13
Gen Vavg LN=14
BUS 1 Hz=15
BUS 1 Vab=16
BUS 1 Vbc=17
BUS 1 Vca=18
Bus 1 Vavg LL=19
Bus 1 VA=20
Bus 1 VB=21
Bus 1 VC=22
Bus 1 Vavg LN=23
BUS 2 Hz=24
BUS 2 VAB=25
BUS 2 VBC=26
BUS 2 VCA=27
Bus 2 Vavg LL=28
Bus 2 VAN=29
Bus 2 VBN=30
Bus 2 VCN=31
Bus 2 Vavg LN=32
Gen PF=33
BUS 1 PF=34
Bus 2 PF=35
Gen Pos kWH=36
Gen Neg kWH=37
Bus 1 Pos kWH=38
Bus 1 Neg kWH=39
Bus 2 Pos kWH=40
Bus 2 Neg kWH=41
Gen IA=42
Gen IB=43
Gen IC=44
Gen I Avg=45
BUS 1 IA=46
BUS 1 IB=47
BUS 1 IC=48
Bus 1 Iavg=49
Bus 2 IAN=50
Bus 2 IBN=51
Bus 2 ICN=52
Bus 2 Iavg=53
IG=54
I AUX=55
GEN kW A=56
GEN kW B=57
GEN kW C=58
GEN kW TOT=59
BUS 1 kW A=60
BUS 1 kW B=61
BUS 1 kW C=62
BUS 1 kW TOT=63
BUS 2 kW A=64
BUS 2 kW B=65
BUS 2 kW C=66
BUS 2 kW TOT=67
GEN kVA A=68
GEN kVA B=69
GEN kVA C=70
GEN kVA TOT=71