Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 247

9469300991 Rev A
241
DGC-2020HD Modbus
™ Protocol
Legacy Register Table
Register
Description
Type
Units
Scaling Factor
R/W
Range
44324
3 Phase Overcurrent Curve
(51-2)
Uint32
n/a
n/a
RW
0 = S1 Curve
1 = S2 Curve
2 = L1 Curve
3 = L2 Curve
4 = D Curve
5 = M Curve
6 = I1 Curve
7 = I2 Curve
8 = V1 Curve
9 = V2 Curve
10 = E1 Curve
11 = E2 Curve
12 = A Curve
13 = B Curve
14 = C Curve
15 = G Curve
16 = F Curve
17 = Programmable
44326
3 Phase Overcurrent Alarm Configuration (51-2)
Uint32
n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44328
1 Phase Overcurrent Pickup
(51-2)
Uint32
CentiAmp
Centi
RW
18 - 775
44330
1 Phase Overcurrent Time Dial (51-2)
Uint32
DeciUnit
Deci
RW
0 - 72000
44332
1 Phase Overcurrent Curve
(51-2)
Uint32
n/a
n/a
RW
0 = S1 Curve
1 = S2 Curve
2 = L1 Curve
3 = L2 Curve
4 = D Curve
5 = M Curve
6 = I1 Curve
7 = I2 Curve
8 = V1 Curve
9 = V2 Curve
10 = E1 Curve
11 = E2 Curve
12 = A Curve
13 = B Curve
14 = C Curve
15 = G Curve
16 = F Curve
17 = Programmable
44334
1 Phase Overcurrent Alarm Configuration (51-2)
Uint32
n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44336
3 Phase Undervoltage Pickup (27-2)
Uint32
Volt
n/a
RW
70 - 576
44338
3 Phase Undervoltage Activation Delay (27-2)
Uint32
Decisecond
Deci
RW
0 - 300
44340
3 Phase Undervoltage Inhibit Frequency (27-2)
Uint32
Hertz
n/a
RW
20 - 90
44342
3 Phase Undervoltage Alarm Configuration (27-2)
Uint32
n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44344
1 Phase Undervoltage Pickup (27-2)
Uint32
Volt
n/a
RW
70 - 576
44346
1 Phase Undervoltage Activation Delay (27-2)
Uint32
Decisecond
Deci
RW
0 - 300
44348
1 Phase Undervoltage Inhibit Frequency (27-2)
Uint32
Hertz
n/a
RW
20 - 90
44350
1 Phase Undervoltage Alarm Configuration (27-2)
Uint32
n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44352
3 Phase Overvoltage Pickup (59-2)
Uint32
Volt
n/a
RW
70 - 576
44354
3 Phase Overvoltage Activation Delay (59-2)
Uint32
Decisecond
Deci
RW
0 - 300
44356
3 Phase Overvoltage Alarm Configuration (59-2)
Uint32
n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44358
1 Phase Overvoltage Pickup (59-2)
Uint32
Volt
n/a
RW
70 - 576
44360
1 Phase Overvoltage Activation Delay (59-2)
Uint32
Decisecond
Deci
RW
0 - 300
44362
1 Phase Overvoltage Alarm Configuration (59-2)
Uint32
n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44364
Overcurrent Low Line Scale Factor (51-2)
Float
n/a
n/a
RW
0.001 - 3
44366
Overvoltage Low Line Scale Factor (59-2)
Float
n/a
n/a
RW
0.001 - 3
44368
Undervoltage Low Line Scale Factor (27-2)
Float
n/a
n/a
RW
0.001 - 3
44370-91
Reserved
44392
3 Phase Reverse Power Pickup
Int32
DeciPercent
Deci
RW
50 - 500
44394
3 Phase Reverse Power Activation Delay
Uint32
Decisecond
Deci
RW
0 - 300