Pulse outputs, Control settings – Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 68

62
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group Register Type Bytes R/W
Unit
Range
Fuel Level Sender Fail
Alarm Configuration
GG
4109
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Fuel Level Sender Fail
Activation Delay
GG
4111
Uint32 4
R W Second 0 - 300
Voltage Sensing Sender
Fail
Alarm Configuration
GG
4113
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Voltage Sensing Sender
Fail
Activation Delay
GG
4115
Uint32 4
R W Second 0 - 300
Single Ph Override
Single-Phase Sense
GG
4117
Uint32 4
R W n/a
AB=0
AC=1
AVR Output
Out-of-Range Activation Delay
GG
4119
Float
4
R W Second 0 - 300
AVR Output
Alarm Configuration
GG
4121
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
GOV Output
Out-of-Range Activation Delay
GG
4123
Float
4
R W Second 0 - 300
GOV Output
Alarm Configuration
GG
4125
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
LS Output
Out of Range Activation Delay
GG
4127
Float
4
R W Second 0 - 300
LS Output
Alarm Configuration
GG
4129
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Pulse Outputs
Name
Description
Group
Register
Type
Bytes
R/W
Unit
Range
AVR Pulse Output
Mode
GG
5000
Uint32
4
R W
n/a
Continuous=0
Proportional=1
AVR Pulse Output
Correction Pulse Width
GG
5002
Float
4
R W
Second
0 - 99.9
AVR Pulse Output
Correction Pulse Interval
GG
5004
Float
4
R W
Second
0 - 99.9
GOV Pulse Output
Mode
GG
5006
Uint32
4
R W
n/a
Continuous=0
Proportional=1
GOV Pulse Output
Correction Pulse Width
GG
5008
Float
4
R W
Second
0 - 99.9
GOV Pulse Output
Correction Pulse Interval
GG
5010
Float
4
R W
Second
0 - 99.9
Control Settings
Name
Description
Group Register Type Bytes R/W Unit
Range
Virtual Switch
Virtual Switch 1 State
GG
5500
Uint32 4
R W n/a
Open=0
Closed=1
Virtual Switch
Virtual Switch 2 State
GG
5502
Uint32 4
R W n/a
Open=0
Closed=1
Virtual Switch
Virtual Switch 3 State
GG
5504
Uint32 4
R W n/a
Open=0
Closed=1
Virtual Switch
Virtual Switch 4 State
GG
5506
Uint32 4
R W n/a
Open=0
Closed=1
Virtual Switch
Virtual Switch 5 State
GG
5508
Uint32 4
R W n/a
Open=0
Closed=1
Virtual Switch
Virtual Switch 6 State
GG
5510
Uint32 4
R W n/a
Open=0
Closed=1
Coms Control Group
Emergency Stop: Writing a 1 will toggle
emergency stop from off to on. Writing a 1
again will toggle emergency stop from on to
off. When read, Off state =0 and On state =1.
GG
5512
Uint32 4
R W n/a
Toggle On/Off=1
Coms Control Group
Remote Start
GG
5514
Uint32 4
R W n/a
Trigger=1
Coms Control Group
Remote Stop
GG
5516
Uint32 4
R W n/a
Trigger=1
Coms Control Group
Run Mode
GG
5518
Uint32 4
R W n/a
Trigger=1
Coms Control Group
Off Mode
GG
5520
Uint32 4
R W n/a
Trigger=1
Coms Control Group
Auto Mode
GG
5522
Uint32 4
R W n/a
Trigger=1
Coms Control Group
Gen Breaker Open Request
GG
5524
Uint32 4
R W n/a
Trigger=1
Coms Control Group
Gen Breaker Close Request
GG
5526
Uint32 4
R W n/a
Trigger=1
Coms Control Group
Mains Breaker Open Request
GG
5528
Uint32 4
R W n/a
Trigger=1
Coms Control Group
Mains Breaker Close Request
GG
5530
Uint32 4
R W n/a
Trigger=1
Coms Control Group
Emergency Stop
GG
5532
Uint32 4
R W n/a
Trigger=1
Coms Control Group
Run Request
GG
5534
Uint32 4
R W n/a
Trigger=1
Coms Control Group
Coms Alarm Reset
GG
5536
Uint32 4
R W n/a
Trigger=1
Coms Control Group
Reset Generator Maximum ROCOF
GG
5538
Uint32 4
R W n/a
Trigger=1
Coms Control Group
Reset Bus 1 Maximum ROCOF
GG
5540
Uint32 4
R W n/a
Trigger=1
Coms Control Group
Reset Bus 2 Maximum ROCOF
GG
5542
Uint32 4
R W n/a
Trigger=1
Coms Control Group
Reset Generator Maximum Vector Shift
GG
5544
Uint32 4
R W n/a
Trigger=1
Coms Control Group
Reset Bus 1 Maximum Vector Shift
GG
5546
Uint32 4
R W n/a
Trigger=1
Coms Control Group
Reset Bus 2 Maximum Vector Shift
GG
5548
Uint32 4
R W n/a
Trigger=1