Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 312

306
9469300991 Rev A
Legacy Register Table
DGC-2020HD Modbus
™ Protocol
Register
Description
Type
Units
Scaling
Factor
R/W
Range
46928
Battery Charge Failed Config Type
Int32
n/a
n/a
RW 0 = None
1 = Alarm
2 = Pre-Alarm
46930
Battery Charge Failed Time Delay
Int32
Second
n/a
RW 0 – 300
46932
Battery Charge Failed Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46934
Fuel Leak Detect Contact Input
Int32
n/a
n/a
RW -1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16
46936
Fuel Leak Detect Config Type
Int32
n/a
n/a
RW 0 = None
1 = Alarm
2 = Pre-Alarm
46938
Fuel Leak Detect Time Delay
Int32
Second
n/a
RW 0 – 300
46940
Fuel Leak Detect Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46942
Single-Phase Connection Override Contact
Input
Int32
n/a
n/a
RW -1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16
46944
Reserved
46946
Single-Phase Connection Override Engine
Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46948
Single-Phase AC Sense Override Contact
Input
Int32
n/a
n/a
RW -1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16
46950
Single-Phase AC Sense Override Time Delay Int32
Second
n/a
RW 0 – 300
46952
Single-Phase AC Sense Override Engine
Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only