Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 67

9469300991 Rev A
61
DGC-2020HD Modbus
™ Protocol
Default Register Table
Name
Description
Group Register Type Bytes R/W
Unit
Range
CEM 1
Enable
GG
4021
Uint32 4
R W n/a
Disabled=0
Enabled=1
CEM 1
CEM Output Configuration
GG
4023
Uint32 4
R W n/a
18 Outputs=0
24 Outputs=1
CEM 2
Enable
GG
4025
Uint32 4
R W n/a
Disabled=0
Enabled=1
CEM 2
CEM Output Configuration
GG
4027
Uint32 4
R W n/a
18 Outputs=0
24 Outputs=1
CEM 3
Enable
GG
4029
Uint32 4
R W n/a
Disabled=0
Enabled=1
CEM 3
CEM Output Configuration
GG
4031
Uint32 4
R W n/a
18 Outputs=0
24 Outputs=1
CEM 4
Enable
GG
4033
Uint32 4
R W n/a
Disabled=0
Enabled=1
CEM 4
CEM Output Configuration
GG
4035
Uint32 4
R W n/a
18 Outputs=0
24 Outputs=1
Genset Controller
Restart Delay
GG
4037
Uint32 4
R W Second 0 - 120
Genset Controller
Cool Down Time
GG
4039
Uint32 4
R W Minute
0 - 60
Genset Controller
Prestart Contact Configuration
GG
4041
Uint32 4
R W n/a
Disabled=0
Enabled=1
Genset Controller
Prestart Rest Configuration
GG
4043
Uint32 4
R W n/a
Off during crank=0
On during rest=1
Preheat before
crank=2
Genset Controller
Cranking Style
GG
4045
Uint32 4
R W n/a
Continuous=0
Cycle=1
Genset Controller
Number of Crank Cycles
GG
4047
Uint32 4
R W n/a
1 - 7
Genset Controller
Cycle Crank Time
GG
4049
Uint32 4
R W Second 5 - 15
Genset Controller
Continuous Crank Time
GG
4051
Uint32 4
R W Second 5 - 60
Genset Controller
Crank Disconnect Limit
GG
4053
Uint32 4
R W Second 10 - 100
Genset Controller
Pre Crank Delay
GG
4055
Uint32 4
R W Second 0 - 30
Genset Controller
Oil Pressure Crank Disconnect
GG
4057
Uint32 4
R W n/a
Disabled=0
Enabled=1
Genset Controller
Crank Disconnect Pressure PSI
GG
4059
Float
4
R W PSI
2.9 - 150
Genset Controller
Crank Disconnect Pressure kPa
GG
4061
Float
4
R W kPa
20 - 1034.5
Genset Controller
Crank Disconnect Pressure bar
GG
4063
Float
4
R W bar
2 - 10.3
Genset Controller
Power Up Delay
GG
4065
Uint32 4
R W Second 0 - 60
Genset Controller
Off Mode Cool Down Enabled
GG
4067
Uint32 4
R W n/a
Disabled=0
Enabled=1
Genset Controller
Remaining Cooldown Time Minutes
GG
4069
Uint32 4
R
Minute
0 - 59
Genset Controller
Remaining Cooldown Time Seconds
GG
4071
Uint32 4
R
Second 0 - 59
Genset Controller
Pending NFPA Level
GG
4073
Uint32 4
R W n/a
Zero=0
One=1
Two=2
Pre-Alarm Enable
Ethernet 1 Link Lost
GG
4075
Uint32 4
R W n/a
Disabled=0
Enabled=1
Pre-Alarm Enable
Ethernet 2 Link Lost
GG
4077
Uint32 4
R W n/a
Disabled=0
Enabled=1
Genset Controller
Gen Reverse Rotation Pre-Alarm
Enable
GG
4079
Uint32 4
R W n/a
Disabled=0
Enabled=1
Genset Controller
Bus 1 Reverse Rotation Pre-Alarm
Enable
GG
4081
Uint32 4
R W n/a
Disabled=0
Enabled=1
Genset Controller
Bus 2 Reverse Rotation Pre-Alarm
Enable
GG
4083
Uint32 4
R W n/a
Disabled=0
Enabled=1
Genset Controller
AEM 1 Comm Fail Pre-Alarm Enable
GG
4085
Uint32 4
R W n/a
Disabled=0
Enabled=1
Genset Controller
AEM 2 Comm Fail Pre-Alarm Enable
GG
4087
Uint32 4
R W n/a
Disabled=0
Enabled=1
Genset Controller
AEM 3 Comm Fail Pre-Alarm Enable
GG
4089
Uint32 4
R W n/a
Disabled=0
Enabled=1
Genset Controller
AEM 4 Comm Fail Pre-Alarm Enable
GG
4091
Uint32 4
R W n/a
Disabled=0
Enabled=1
Genset Controller
CEM 1 Comm Fail Pre-Alarm Enable
GG
4093
Uint32 4
R W n/a
Disabled=0
Enabled=1
Genset Controller
CEM 2 Comm Fail Pre-Alarm Enable
GG
4095
Uint32 4
R W n/a
Disabled=0
Enabled=1
Genset Controller
CEM 3 Comm Fail Pre-Alarm Enable
GG
4097
Uint32 4
R W n/a
Disabled=0
Enabled=1
Genset Controller
CEM 4 Comm Fail Pre-Alarm Enable
GG
4099
Uint32 4
R W n/a
Disabled=0
Enabled=1
Coolant Temp Sender Fail Alarm Configuration
GG
4101
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Coolant Temp Sender Fail Coolant Activation Delay
GG
4103
Uint32 4
R W Second 300 - 1800
Oil Pressure Sender Fail
Alarm Configuration
GG
4105
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Oil Pressure Sender Fail
Activation Delay
GG
4107
Uint32 4
R W Second 0 - 300