9469300991 Rev A

61

DGC-2020HD Modbus

™ Protocol

Default Register Table

Name

Description

Group Register Type Bytes R/W

Unit

Range

CEM 1

Enable

GG

4021

Uint32 4

R W n/a

Disabled=0
Enabled=1

CEM 1

CEM Output Configuration

GG

4023

Uint32 4

R W n/a

18 Outputs=0
24 Outputs=1

CEM 2

Enable

GG

4025

Uint32 4

R W n/a

Disabled=0
Enabled=1

CEM 2

CEM Output Configuration

GG

4027

Uint32 4

R W n/a

18 Outputs=0
24 Outputs=1

CEM 3

Enable

GG

4029

Uint32 4

R W n/a

Disabled=0

Enabled=1

CEM 3

CEM Output Configuration

GG

4031

Uint32 4

R W n/a

18 Outputs=0

24 Outputs=1

CEM 4

Enable

GG

4033

Uint32 4

R W n/a

Disabled=0

Enabled=1

CEM 4

CEM Output Configuration

GG

4035

Uint32 4

R W n/a

18 Outputs=0

24 Outputs=1

Genset Controller

Restart Delay

GG

4037

Uint32 4

R W Second 0 - 120

Genset Controller

Cool Down Time

GG

4039

Uint32 4

R W Minute

0 - 60

Genset Controller

Prestart Contact Configuration

GG

4041

Uint32 4

R W n/a

Disabled=0
Enabled=1

Genset Controller

Prestart Rest Configuration

GG

4043

Uint32 4

R W n/a

Off during crank=0

On during rest=1

Preheat before
crank=2

Genset Controller

Cranking Style

GG

4045

Uint32 4

R W n/a

Continuous=0
Cycle=1

Genset Controller

Number of Crank Cycles

GG

4047

Uint32 4

R W n/a

1 - 7

Genset Controller

Cycle Crank Time

GG

4049

Uint32 4

R W Second 5 - 15

Genset Controller

Continuous Crank Time

GG

4051

Uint32 4

R W Second 5 - 60

Genset Controller

Crank Disconnect Limit

GG

4053

Uint32 4

R W Second 10 - 100

Genset Controller

Pre Crank Delay

GG

4055

Uint32 4

R W Second 0 - 30

Genset Controller

Oil Pressure Crank Disconnect

GG

4057

Uint32 4

R W n/a

Disabled=0

Enabled=1

Genset Controller

Crank Disconnect Pressure PSI

GG

4059

Float

4

R W PSI

2.9 - 150

Genset Controller

Crank Disconnect Pressure kPa

GG

4061

Float

4

R W kPa

20 - 1034.5

Genset Controller

Crank Disconnect Pressure bar

GG

4063

Float

4

R W bar

2 - 10.3

Genset Controller

Power Up Delay

GG

4065

Uint32 4

R W Second 0 - 60

Genset Controller

Off Mode Cool Down Enabled

GG

4067

Uint32 4

R W n/a

Disabled=0

Enabled=1

Genset Controller

Remaining Cooldown Time Minutes

GG

4069

Uint32 4

R

Minute

0 - 59

Genset Controller

Remaining Cooldown Time Seconds

GG

4071

Uint32 4

R

Second 0 - 59

Genset Controller

Pending NFPA Level

GG

4073

Uint32 4

R W n/a

Zero=0
One=1

Two=2

Pre-Alarm Enable

Ethernet 1 Link Lost

GG

4075

Uint32 4

R W n/a

Disabled=0

Enabled=1

Pre-Alarm Enable

Ethernet 2 Link Lost

GG

4077

Uint32 4

R W n/a

Disabled=0

Enabled=1

Genset Controller

Gen Reverse Rotation Pre-Alarm
Enable

GG

4079

Uint32 4

R W n/a

Disabled=0
Enabled=1

Genset Controller

Bus 1 Reverse Rotation Pre-Alarm
Enable

GG

4081

Uint32 4

R W n/a

Disabled=0
Enabled=1

Genset Controller

Bus 2 Reverse Rotation Pre-Alarm
Enable

GG

4083

Uint32 4

R W n/a

Disabled=0
Enabled=1

Genset Controller

AEM 1 Comm Fail Pre-Alarm Enable

GG

4085

Uint32 4

R W n/a

Disabled=0

Enabled=1

Genset Controller

AEM 2 Comm Fail Pre-Alarm Enable

GG

4087

Uint32 4

R W n/a

Disabled=0

Enabled=1

Genset Controller

AEM 3 Comm Fail Pre-Alarm Enable

GG

4089

Uint32 4

R W n/a

Disabled=0

Enabled=1

Genset Controller

AEM 4 Comm Fail Pre-Alarm Enable

GG

4091

Uint32 4

R W n/a

Disabled=0

Enabled=1

Genset Controller

CEM 1 Comm Fail Pre-Alarm Enable

GG

4093

Uint32 4

R W n/a

Disabled=0

Enabled=1

Genset Controller

CEM 2 Comm Fail Pre-Alarm Enable

GG

4095

Uint32 4

R W n/a

Disabled=0
Enabled=1

Genset Controller

CEM 3 Comm Fail Pre-Alarm Enable

GG

4097

Uint32 4

R W n/a

Disabled=0
Enabled=1

Genset Controller

CEM 4 Comm Fail Pre-Alarm Enable

GG

4099

Uint32 4

R W n/a

Disabled=0
Enabled=1

Coolant Temp Sender Fail Alarm Configuration

GG

4101

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

Coolant Temp Sender Fail Coolant Activation Delay

GG

4103

Uint32 4

R W Second 300 - 1800

Oil Pressure Sender Fail

Alarm Configuration

GG

4105

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

Oil Pressure Sender Fail

Activation Delay

GG

4107

Uint32 4

R W Second 0 - 300