beautypg.com

Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 76

background image

70

9469300991 Rev A

Default Register Table

DGC-2020HD Modbus

™ Protocol

Name

Description

Group Register Type Bytes R/W

Unit

Range

AEM 1 Input Config. 8

Param Min

GG

7098

Float

4

R W n/a

-999999 - 999999

AEM 1 Input Config. 8

Param Max

GG

7100

Float

4

R W n/a

-999999 - 999999

AEM 1 Input Config. 8

Current Min

GG

7102

Float

4

R W Milliamp 4 - 20

AEM 1 Input Config. 8

Current Max

GG

7104

Float

4

R W Milliamp 4 - 20

AEM 1 Input Config. 8

Voltage Min

GG

7106

Float

4

R W Volt

0 - 10

AEM 1 Input Config. 8

Voltage Max

GG

7108

Float

4

R W Volt

0 - 10

AEM 1 Input Config. 8

Alarm Configuration

GG

7110

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

AEM 1 Protection 1

Hysteresis

GG

7112

Float

4

R W Percent 0 - 100

AEM 1 Protection 1

Arming Delay

GG

7114

Float

4

R W Second 0 - 300

AEM 1 Protection 1

Threshold 1 Pickup

GG

7116

Float

4

R W n/a

-999999 - 999999

AEM 1 Protection 1

Threshold 1 Activation Delay GG

7118

Float

4

R W Second 0 - 300

AEM 1 Protection 1

Threshold 1 Alarm
Configuration

GG

7120

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

AEM 1 Protection 1

Threshold 2 Pickup

GG

7122

Float

4

R W n/a

-999999 - 999999

AEM 1 Protection 1

Threshold 2 Activation Delay GG

7124

Float

4

R W Second 0 - 300

AEM 1 Protection 1

Threshold 2 Alarm
Configuration

GG

7126

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

AEM 1 Protection 1

Threshold 3P ickup

GG

7128

Float

4

R W n/a

-999999 - 999999

AEM 1 Protection 1

Threshold 3 Activation Delay GG

7130

Float

4

R W Second 0 - 300

AEM 1 Protection 1

Threshold 3 Alarm
Configuration

GG

7132

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

AEM 1 Protection 1

Threshold 4 Pickup

GG

7134

Float

4

R W n/a

-999999 - 999999

AEM 1 Protection 1

Threshold 4 Activation Delay GG

7136

Float

4

R W Second 0 - 300

AEM 1 Protection 1

Threshold 4 Alarm
Configuration

GG

7138

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

AEM 1 Protection 2

Hysteresis

GG

7140

Float

4

R W Percent 0 - 100

AEM 1 Protection 2

Arming Delay

GG

7142

Float

4

R W Second 0 - 300

AEM 1 Protection 2

Threshold 1 Pickup

GG

7144

Float

4

R W n/a

-999999 - 999999

AEM 1 Protection 2

Threshold 1 Activation Delay GG

7146

Float

4

R W Second 0 - 300

AEM 1 Protection 2

Threshold 1 Alarm

Configuration

GG

7148

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1

Alarm=2

AEM 1 Protection 2

Threshold 2 Pickup

GG

7150

Float

4

R W n/a

-999999 - 999999

AEM 1 Protection 2

Threshold 2 Activation Delay GG

7152

Float

4

R W Second 0 - 300

AEM 1 Protection 2

Threshold 2 Alarm
Configuration

GG

7154

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

AEM 1 Protection 2

Threshold 3 Pickup

GG

7156

Float

4

R W n/a

-999999 - 999999

AEM 1 Protection 2

Threshold 3 Activation Delay GG

7158

Float

4

R W Second 0 - 300

AEM 1 Protection 2

Threshold 3 Alarm
Configuration

GG

7160

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

AEM 1 Protection 2

Threshold 4 Pickup

GG

7162

Float

4

R W n/a

-999999 - 999999

AEM 1 Protection 2

Threshold 4 Activation Delay GG

7164

Float

4

R W Second 0 - 300

AEM 1 Protection 2

Threshold 4 Alarm
Configuration

GG

7166

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

AEM 1 Protection 3

Hysteresis

GG

7168

Float

4

R W Percent 0 - 100

AEM 1 Protection 3

Arming Delay

GG

7170

Float

4

R W Second 0 - 300

AEM 1 Protection 3

Threshold 1 Pickup

GG

7172

Float

4

R W n/a

-999999 - 999999

AEM 1 Protection 3

Threshold 1 Activation Delay GG

7174

Float

4

R W Second 0 - 300

AEM 1 Protection 3

Threshold 1 Alarm

Configuration

GG

7176

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1

Alarm=2

AEM 1 Protection 3

Threshold 2 Pickup

GG

7178

Float

4

R W n/a

-999999 - 999999

AEM 1 Protection 3

Threshold 2 Activation Delay GG

7180

Float

4

R W Second 0 - 300

AEM 1 Protection 3

Threshold 2 Alarm
Configuration

GG

7182

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

AEM 1 Protection 3

Threshold 3 Pickup

GG

7184

Float

4

R W n/a

-999999 - 999999

AEM 1 Protection 3

Threshold 3 Activation Delay GG

7186

Float

4

R W Second 0 - 300

AEM 1 Protection 3

Threshold 3 Alarm
Configuration

GG

7188

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

AEM 1 Protection 3

Threshold 4 Pickup

GG

7190

Float

4

R W n/a

-999999 - 999999

AEM 1 Protection 3

Threshold 4 Activation Delay GG

7192

Float

4

R W Second 0 - 300

AEM 1 Protection 3

Threshold 4 Alarm
Configuration

GG

7194

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

AEM 1 Protection 4

Hysteresis

GG

7196

Float

4

R W Percent 0 - 100

AEM 1 Protection 4

Arming Delay

GG

7198

Float

4

R W Second 0 - 300