70
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group Register Type Bytes R/W
Unit
Range
AEM 1 Input Config. 8
Param Min
GG
7098
Float
4
R W n/a
-999999 - 999999
AEM 1 Input Config. 8
Param Max
GG
7100
Float
4
R W n/a
-999999 - 999999
AEM 1 Input Config. 8
Current Min
GG
7102
Float
4
R W Milliamp 4 - 20
AEM 1 Input Config. 8
Current Max
GG
7104
Float
4
R W Milliamp 4 - 20
AEM 1 Input Config. 8
Voltage Min
GG
7106
Float
4
R W Volt
0 - 10
AEM 1 Input Config. 8
Voltage Max
GG
7108
Float
4
R W Volt
0 - 10
AEM 1 Input Config. 8
Alarm Configuration
GG
7110
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 1 Protection 1
Hysteresis
GG
7112
Float
4
R W Percent 0 - 100
AEM 1 Protection 1
Arming Delay
GG
7114
Float
4
R W Second 0 - 300
AEM 1 Protection 1
Threshold 1 Pickup
GG
7116
Float
4
R W n/a
-999999 - 999999
AEM 1 Protection 1
Threshold 1 Activation Delay GG
7118
Float
4
R W Second 0 - 300
AEM 1 Protection 1
Threshold 1 Alarm
Configuration
GG
7120
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 1 Protection 1
Threshold 2 Pickup
GG
7122
Float
4
R W n/a
-999999 - 999999
AEM 1 Protection 1
Threshold 2 Activation Delay GG
7124
Float
4
R W Second 0 - 300
AEM 1 Protection 1
Threshold 2 Alarm
Configuration
GG
7126
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 1 Protection 1
Threshold 3P ickup
GG
7128
Float
4
R W n/a
-999999 - 999999
AEM 1 Protection 1
Threshold 3 Activation Delay GG
7130
Float
4
R W Second 0 - 300
AEM 1 Protection 1
Threshold 3 Alarm
Configuration
GG
7132
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 1 Protection 1
Threshold 4 Pickup
GG
7134
Float
4
R W n/a
-999999 - 999999
AEM 1 Protection 1
Threshold 4 Activation Delay GG
7136
Float
4
R W Second 0 - 300
AEM 1 Protection 1
Threshold 4 Alarm
Configuration
GG
7138
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 1 Protection 2
Hysteresis
GG
7140
Float
4
R W Percent 0 - 100
AEM 1 Protection 2
Arming Delay
GG
7142
Float
4
R W Second 0 - 300
AEM 1 Protection 2
Threshold 1 Pickup
GG
7144
Float
4
R W n/a
-999999 - 999999
AEM 1 Protection 2
Threshold 1 Activation Delay GG
7146
Float
4
R W Second 0 - 300
AEM 1 Protection 2
Threshold 1 Alarm
Configuration
GG
7148
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 1 Protection 2
Threshold 2 Pickup
GG
7150
Float
4
R W n/a
-999999 - 999999
AEM 1 Protection 2
Threshold 2 Activation Delay GG
7152
Float
4
R W Second 0 - 300
AEM 1 Protection 2
Threshold 2 Alarm
Configuration
GG
7154
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 1 Protection 2
Threshold 3 Pickup
GG
7156
Float
4
R W n/a
-999999 - 999999
AEM 1 Protection 2
Threshold 3 Activation Delay GG
7158
Float
4
R W Second 0 - 300
AEM 1 Protection 2
Threshold 3 Alarm
Configuration
GG
7160
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 1 Protection 2
Threshold 4 Pickup
GG
7162
Float
4
R W n/a
-999999 - 999999
AEM 1 Protection 2
Threshold 4 Activation Delay GG
7164
Float
4
R W Second 0 - 300
AEM 1 Protection 2
Threshold 4 Alarm
Configuration
GG
7166
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 1 Protection 3
Hysteresis
GG
7168
Float
4
R W Percent 0 - 100
AEM 1 Protection 3
Arming Delay
GG
7170
Float
4
R W Second 0 - 300
AEM 1 Protection 3
Threshold 1 Pickup
GG
7172
Float
4
R W n/a
-999999 - 999999
AEM 1 Protection 3
Threshold 1 Activation Delay GG
7174
Float
4
R W Second 0 - 300
AEM 1 Protection 3
Threshold 1 Alarm
Configuration
GG
7176
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 1 Protection 3
Threshold 2 Pickup
GG
7178
Float
4
R W n/a
-999999 - 999999
AEM 1 Protection 3
Threshold 2 Activation Delay GG
7180
Float
4
R W Second 0 - 300
AEM 1 Protection 3
Threshold 2 Alarm
Configuration
GG
7182
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 1 Protection 3
Threshold 3 Pickup
GG
7184
Float
4
R W n/a
-999999 - 999999
AEM 1 Protection 3
Threshold 3 Activation Delay GG
7186
Float
4
R W Second 0 - 300
AEM 1 Protection 3
Threshold 3 Alarm
Configuration
GG
7188
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 1 Protection 3
Threshold 4 Pickup
GG
7190
Float
4
R W n/a
-999999 - 999999
AEM 1 Protection 3
Threshold 4 Activation Delay GG
7192
Float
4
R W Second 0 - 300
AEM 1 Protection 3
Threshold 4 Alarm
Configuration
GG
7194
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 1 Protection 4
Hysteresis
GG
7196
Float
4
R W Percent 0 - 100
AEM 1 Protection 4
Arming Delay
GG
7198
Float
4
R W Second 0 - 300