Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 121
9469300991 Rev A
115
DGC-2020HD Modbus
™ Protocol
Default Register Table
Name
Description
Group Register Type Bytes R/W
Unit
Range
AEM 4 Remote Analog
Output 1
Out-of-Range Activation
Delay
GG
8562
Float
4
R W Second 0 - 300
AEM 4 Remote Analog
Output 1
Parameter Minimum
GG
8564
Float
4
R W n/a
-999999 - 999999
AEM 4 Remote Analog
Output 1
Parameter Maximum
GG
8566
Float
4
R W n/a
-999999 - 999999
AEM 4 Remote Analog
Output 1
Current Minimum
GG
8568
Float
4
R W Milliamp 4 - 20
AEM 4 Remote Analog
Output 1
Current Maximum
GG
8570
Float
4
R W Milliamp 4 - 20
AEM 4 Remote Analog
Output 1
Voltage Minimum
GG
8572
Float
4
R W Volt
0 - 10
AEM 4 Remote Analog
Output 1
Voltage Maximum
GG
8574
Float
4
R W Volt
0 - 10
AEM 4 Remote Analog
Output 1
Alarm Configuration
GG
8576
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Remote Analog
Output 2
Parameter Selection
GG
8578
Int32
4
R W n/a
No Parameter=0
Oil Pressure=1
Coolant Temp=2
Battery Volts=3
RPM=4
Fuel Level=5
Gen Hz=6
Gen VAB=7
Gen VBC=8
Gen VCA=9
Gen Vavg LL=10
Gen VAN=11
Gen VBN=12
Gen VCN=13
Gen Vavg LN=14
Bus 1 Hz=15
Bus 1 VAB=16
Bus 1 VBC=17
Bus 1 VCA=18
Bus 1 Vavg LL=19
Bus 1 VA=20
Bus 1 VB=21
Bus 1 VC=22
Bus 1 Vavg LN=23
Bus 2 Hz=24
Bus 2 VAB=25
Bus 2 VBC=26
Bus 2 VCA=27
Bus 2 Vavg LL=28
Bus 2 VAN=29
Bus 2 VBN=30
Bus 2 VCN=31
Bus 2 Vavg LN=32
Gen PF=33
Bus 1 PF=34
Bus 2 PF=35
Gen Pos kWh=36
Gen Neg kWh=37
Bus 1 Pos kWh=38
Bus 1 Neg kWh=39
Bus 2 Pos kWh=40
Bus 2 Neg kWh=41
Gen IA=42
Gen IB=43
Gen IC=44
Gen I Avg=45
Bus 1 IA=46
Bus 1 IB=47
Bus 1 IC=48
Bus 1 Iavg=49
Bus 2 IAN=50
Bus 2 IBN=51
Bus 2 ICN=52
Bus 2 Iavg=53
IG=54
I Aux=55
Gen kW A=56
Gen kW B=57
Gen kW C=58
Gen kW Total=59
Bus 1 kW A=60
Bus 1 kW B=61
Bus 1 kW C=62
Bus 1 kW Total=63