Legacy Register Table

DGC-2020HD Modbus

™ Protocol

Bias Control Settings

Register

Description

Type

Units

Scaling Factor

R/W

Range

42250

AVR Kp Proportional Gain

Float

n/a

n/a

RW

0 - 1000

42252

AVR Ki Integral Gain

Float

n/a

n/a

RW

0 - 1000

42254

AVR Kd Derivative Gain

Float

n/a

n/a

RW

0 - 1000

42256

AVR Td Filter Constant

Float

n/a

n/a

RW

0 - 1

42258

AVR Kg Loop Gain

Float

n/a

n/a

RW

0 - 1000

42260

AVR Windup Limit

Int32

n/a

n/a

RW

0 = Disable
1 = Enable

42262

AVR Integrator Limit Plus

Float

n/a

n/a

RW

0 - 1000

42264

AVR Integrator Limit Minus

Float

n/a

n/a

RW

(-1000) - 0

42266

AVR Output Upper Limit

Float

n/a

n/a

RW

0 - 1000

42268

AVR Output Lower Limit

Float

n/a

n/a

RW

(-1000) - 0

42270

Reserved

42272

Governor Kp Proportional Gain

Float

n/a

n/a

RW

0 - 1000

42274

Governor Ki Integral Gain

Float

n/a

n/a

RW

0 - 1000

42276

Governor Kd Derivative Gain

Float

n/a

n/a

RW

0 - 1000

42278

Governor Td Filter Constant

Float

n/a

n/a

RW

0 - 1

42280

Governor Loop Gain

Float

n/a

n/a

RW

0 - 1000

42282

Governor Windup Limit

Int32

n/a

n/a

RW

0 = Disable
1 = Enable

42284

Governor Integrator Limit Plus

Float

n/a

n/a

RW

0 - 1000

42286

Governor Integrator Limit Minus

Float

n/a

n/a

RW

(-1000) - 0

42288

Governor Output Upper Limit

Float

n/a

n/a

RW

0 - 1000

42290

Governor Output Lower Limit

Float

n/a

n/a

RW

(-1000) - 0

42292

Reserved

42294

kvar Kp

Float

n/a

n/a

RW

0 - 1000

42296

kvar Ki

Float

n/a

n/a

RW

0 - 1000

42298

kvar Kd

Float

n/a

n/a

RW

0 - 1000

42300

kvar Td

Float

n/a

n/a

RW

0 - 1

42302

kvar Loop Gain

Float

n/a

n/a

RW

0 - 1000

42304

kvar Windup Limit

Int32

n/a

n/a

RW

0 = Disable
1 = Enable

42306

kvar Integrator Limit Plus

Float

n/a

n/a

RW

0 - 1000

42308

kvar Integrator Limit Minus

Float

N//A

n/a

RW

(-1000) - 0

42310

kvar Output Upper Limit

Float

n/a

n/a

RW

0 - 1000

42312

kvar Output Lower Limit

Float

n/a

n/a

RW

(-1000) - 0

42314

Reserved

42316

kW Kp

Float

n/a

n/a

RW

0 - 1000

42318

kW Ki

Float

n/a

n/a

RW

0 - 1000

42320

kW Kd

Float

n/a

n/a

RW

0 - 1000

42322

kW Td

Float

n/a

n/a

RW

0 - 1

42324

kW Loop Gain

Float

n/a

n/a

RW

0 - 1000

42326

kW Windup Limit

Int32

n/a

n/a

RW

0 = Disable
1 = Enable

42328

kW Integrator Limit Plus

Float

n/a

n/a

RW

0 - 1000

42330

kW Integrator Limit Minus

Float

n/a

n/a

RW

(-1000) - 0

42332

kW Output Upper Limit

Float

n/a

n/a

RW

0 - 1000

42334

kW Output Lower Limit

Float

n/a

n/a

RW

(-1000) - 0

42336

Reserved

42338

Droop Percent

Float

Percent

n/a

RW

0 - 10

42340

Load Control

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

42342

kW Load Rate

Int32

n/a

Deci

RW

0 - 1000

42344

Breaker Open Setpoint

Int32

n/a

Deci

RW

0 - 1000

42346

AVR Bias Control Output Type

Int32

n/a

n/a

RW

0 = Contact
1 = Analog

42348

Governor Bias Control Output Type

Int32

n/a

n/a

RW

0 = Contact
1 = Analog

42350

Speed Droop Gain

Float

n/a

n/a

RW

0 - 1000

42352

Voltage Droop Gain

Float

n/a

n/a

RW

0 - 1000

42354

Speed Trim Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

42356

Voltage Trim Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

42358

Ramped Watt Demand Per Unit

Float

n/a

n/a

R

0 - 100

42360

Watt Demand Per Unit

Float

n/a

n/a

R

0 - 100

42362

Speed PID Output

Float

n/a

n/a

R

0 - 100

42364

kW PID Output

Float

n/a

n/a

R

0 - 100

42366

Volt PID Output

Float

n/a

n/a

R

0 - 100

42368

Speed Trim Setpoint

Uint32

DeciHertz

Centi

RW

4700 - 44000

42370

var Control Enable

Int32

n/a

n/a

RW

0 = Disable
1 = Enable

42372

kvar Load Rate

Uint32

n/a

Deci

RW

1 - 1000