Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 64

58
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group
Register
Type
Bytes
R/W
Unit
Range
Bus1 Condition
Alternate Frequency Scale
SG0 3P
3278
Float
4
R W
n/a
0.001 - 100
Bus1 Condition
Dead Pickup
SG1 1P
3280
Float
4
R W
Volt
0 - 4800
Bus1 Condition
Dead Time Delay
SG1 1P
3282
Float
4
R W
Second
0.1 - 600
Bus1 Condition
Stable Undervoltage Pickup
SG1 1P
3284
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Undervoltage Dropout
SG1 1P
3286
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Overvoltage Pickup
SG1 1P
3288
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Overvoltage Dropout
SG1 1P
3290
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Underfrequency Pickup
SG1 1P
3292
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Underfrequency Dropout
SG1 1P
3294
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Overfrequency Pickup
SG1 1P
3296
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Overfrequency Dropout
SG1 1P
3298
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Time Delay
SG1 1P
3300
Float
4
R W
Second
0.1 - 600
Bus1 Condition
Fail Time Delay
SG1 1P
3302
Float
4
R W
Second
0.1 - 600
Bus1 Condition
Low-Line Scale
SG1 1P
3304
Float
4
R W
n/a
0.001 - 3
Bus1 Condition
Alternate Frequency Scale
SG1 1P
3306
Float
4
R W
n/a
0.001 - 100
Bus1 Condition
Dead Pickup
SG1 3P
3308
Float
4
R W
Volt
0 - 4800
Bus1 Condition
Dead Time Delay
SG1 3P
3310
Float
4
R W
Second
0.1 - 600
Bus1 Condition
Stable Undervoltage Pickup
SG1 3P
3312
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Undervoltage Dropout
SG1 3P
3314
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Overvoltage Pickup
SG1 3P
3316
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Overvoltage Dropout
SG1 3P
3318
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Underfrequency Pickup
SG1 3P
3320
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Underfrequency Dropout
SG1 3P
3322
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Overfrequency Pickup
SG1 3P
3324
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Overfrequency Dropout
SG1 3P
3326
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Time Delay
SG1 3P
3328
Float
4
R W
Second
0.1 - 600
Bus1 Condition
Fail Time Delay
SG1 3P
3330
Float
4
R W
Second
0.1 - 600
Bus1 Condition
Low-Line Scale
SG1 3P
3332
Float
4
R W
n/a
0.001 - 3
Bus1 Condition
Alternate Frequency Scale
SG1 3P
3334
Float
4
R W
n/a
0.001 - 100
Bus1 Condition
Dead Pickup
SG2 1P
3336
Float
4
R W
Volt
0 - 4800
Bus1 Condition
Dead Time Delay
SG2 1P
3338
Float
4
R W
Second
0.1 - 600
Bus1 Condition
Stable Undervoltage Pickup
SG2 1P
3340
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Undervoltage Dropout
SG2 1P
3342
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Overvoltage Pickup
SG2 1P
3344
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Overvoltage Dropout
SG2 1P
3346
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Underfrequency Pickup
SG2 1P
3348
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Underfrequency Dropout
SG2 1P
3350
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Overfrequency Pickup
SG2 1P
3352
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Overfrequency Dropout
SG2 1P
3354
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Time Delay
SG2 1P
3356
Float
4
R W
Second
0.1 - 600
Bus1 Condition
Fail Time Delay
SG2 1P
3358
Float
4
R W
Second
0.1 - 600
Bus1 Condition
Low-Line Scale
SG2 1P
3360
Float
4
R W
n/a
0.001 - 3
Bus1 Condition
Alternate Frequency Scale
SG2 1P
3362
Float
4
R W
n/a
0.001 - 100
Bus1 Condition
Dead Pickup
SG2 3P
3364
Float
4
R W
Volt
0 - 4800
Bus1 Condition
Dead Time Delay
SG2 3P
3366
Float
4
R W
Second
0.1 - 600
Bus1 Condition
Stable Undervoltage Pickup
SG2 3P
3368
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Undervoltage Dropout
SG2 3P
3370
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Overvoltage Pickup
SG2 3P
3372
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Overvoltage Dropout
SG2 3P
3374
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Underfrequency Pickup
SG2 3P
3376
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Underfrequency Dropout
SG2 3P
3378
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Overfrequency Pickup
SG2 3P
3380
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Overfrequency Dropout
SG2 3P
3382
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Time Delay
SG2 3P
3384
Float
4
R W
Second
0.1 - 600
Bus1 Condition
Fail Time Delay
SG2 3P
3386
Float
4
R W
Second
0.1 - 600
Bus1 Condition
Low-Line Scale
SG2 3P
3388
Float
4
R W
n/a
0.001 - 3
Bus1 Condition
Alternate Frequency Scale
SG2 3P
3390
Float
4
R W
n/a
0.001 - 100
Bus1 Condition
Dead Pickup
SG3 1P
3392
Float
4
R W
Volt
0 - 4800
Bus1 Condition
Dead Time Delay
SG3 1P
3394
Float
4
R W
Second
0.1 - 600
Bus1 Condition
Stable Undervoltage Pickup
SG3 1P
3396
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Undervoltage Dropout
SG3 1P
3398
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Overvoltage Pickup
SG3 1P
3400
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Overvoltage Dropout
SG3 1P
3402
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Underfrequency Pickup
SG3 1P
3404
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Underfrequency Dropout
SG3 1P
3406
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Overfrequency Pickup
SG3 1P
3408
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Overfrequency Dropout
SG3 1P
3410
Float
4
R W
Hertz
46 - 64
Bus1 Condition
Stable Time Delay
SG3 1P
3412
Float
4
R W
Second
0.1 - 600
Bus1 Condition
Fail Time Delay
SG3 1P
3414
Float
4
R W
Second
0.1 - 600
Bus1 Condition
Low-Line Scale
SG3 1P
3416
Float
4
R W
n/a
0.001 - 3
Bus1 Condition
Alternate Frequency Scale
SG3 1P
3418
Float
4
R W
n/a
0.001 - 100
Bus1 Condition
Dead Pickup
SG3 3P
3420
Float
4
R W
Volt
0 - 4800
Bus1 Condition
Dead Time Delay
SG3 3P
3422
Float
4
R W
Second
0.1 - 600
Bus1 Condition
Stable Undervoltage Pickup
SG3 3P
3424
Float
4
R W
Volt
10 - 99999
Bus1 Condition
Stable Undervoltage Dropout
SG3 3P
3426
Float
4
R W
Volt
10 - 99999