Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 22
16
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group Register Type Bytes R/W
Unit
Range
Single-Phase Override Contact Input
GG
0368
Uint32 4
R W n/a
None=0
Input 1=1
Input 2=2
Input 3=3
Input 4=4
Input 5=5
Input 6=6
Input 7=7
Input 8=8
Input 9=9
Input 10=10
Input 11=11
Input 12=12
Input 13=13
Input 14=14
Input 15=15
Input 16=16
Single-Phase Override Contact Recognition
GG
0370
Uint32 4
R W n/a
Always=0
Engine Running=1
Config Element 1
Contact Recognition
GG
0372
Uint32 4
R W n/a
Always=0
Engine Running=1
Config Element 1
Alarm Configuration
GG
0374
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Element 1
Activation Delay
GG
0376
Uint32 4
R W Second
0 - 300
Config Element 2
Contact Recognition
GG
0378
Uint32 4
R W n/a
Always=0
Engine Running=1
Config Element 2
Alarm Configuration
GG
0380
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Element 2
Activation Delay
GG
0382
Uint32 4
R W Second
0 - 300
Config Element 3
Contact Recognition
GG
0384
Uint32 4
R W n/a
Always=0
Engine Running=1
Config Element 3
Alarm Configuration
GG
0386
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Element 3
Activation Delay
GG
0388
Uint32 4
R W Second
0 - 300
Config Element 4
Contact Recognition
GG
0390
Uint32 4
R W n/a
Always=0
Engine Running=1
Config Element 4
Alarm Configuration
GG
0392
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Element 4
Activation Delay
GG
0394
Uint32 4
R W Second
0 - 300
Config Element 5
Contact Recognition
GG
0396
Uint32 4
R W n/a
Always=0
Engine Running=1
Config Element 5
Alarm Configuration
GG
0398
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Element 5
Activation Delay
GG
0400
Uint32 4
R W Second
0 - 300
Config Element 6
Contact Recognition
GG
0402
Uint32 4
R W n/a
Always=0
Engine Running=1
Config Element 6
Alarm Configuration
GG
0404
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Element 6
Activation Delay
GG
0406
Uint32 4
R W Second
0 - 300
Config Element 7
Contact Recognition
GG
0408
Uint32 4
R W n/a
Always=0
Engine Running=1
Config Element 7
Alarm Configuration
GG
0410
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Element 7
Activation Delay
GG
0412
Uint32 4
R W Second
0 - 300
Config Element 8
Contact Recognition
GG
0414
Uint32 4
R W n/a
Always=0
Engine Running=1
Config Element 8
Alarm Configuration
GG
0416
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Element 8
Activation Delay
GG
0418
Uint32 4
R W Second
0 - 300
Contact Input 1
Contact Recognition
GG
0420
Uint32 4
R W n/a
Always=0
Engine Running=1
Contact Input 1
Alarm Configuration
GG
0422
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Contact Input 1
Activation Delay
GG
0424
Uint32 4
R W Second
0 - 300
Contact Input 2
Contact Recognition
GG
0426
Uint32 4
R W n/a
Always=0
Engine Running=1
Contact Input 2
Alarm Configuration
GG
0428
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Contact Input 2
Activation Delay
GG
0430
Uint32 4
R W Second
0 - 300