Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 118

112
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group Register Type Bytes R/W
Unit
Range
AEM 4 Protection 6
Threshold 3 Alarm
Configuration
GG
8496
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 6
Threshold 4 Pickup
GG
8498
Float
4
R W n/a
-999999 - 999999
AEM 4 Protection 6
Threshold 4 Activation Delay GG
8500
Float
4
R W Second 0 - 300
AEM 4 Protection 6
Threshold 4 Alarm
Configuration
GG
8502
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 7
Hysteresis
GG
8504
Float
4
R W Percent 0 - 100
AEM 4 Protection 7
Arming Delay
GG
8506
Float
4
R W Second 0 - 300
AEM 4 Protection 7
Threshold 1 Pickup
GG
8508
Float
4
R W n/a
-999999 - 999999
AEM 4 Protection 7
Threshold 1 Activation Delay GG
8510
Float
4
R W Second 0 - 300
AEM 4 Protection 7
Threshold 1 Alarm
Configuration
GG
8512
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 7
Threshold 2 Pickup
GG
8514
Float
4
R W n/a
-999999 - 999999
AEM 4 Protection 7
Threshold 2 Activation Delay GG
8516
Float
4
R W Second 0 - 300
AEM 4 Protection 7
Threshold 2 Alarm
Configuration
GG
8518
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 7
Threshold 3 Pickup
GG
8520
Float
4
R W n/a
-999999 - 999999
AEM 4 Protection 7
Threshold 3 Activation Delay GG
8522
Float
4
R W Second 0 - 300
AEM 4 Protection 7
Threshold 3 Alarm
Configuration
GG
8524
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 7
Threshold 4 Pickup
GG
8526
Float
4
R W n/a
-999999 - 999999
AEM 4 Protection 7
Threshold 4 Activation Delay GG
8528
Float
4
R W Second 0 - 300
AEM 4 Protection 7
Threshold 4 Alarm
Configuration
GG
8530
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 8
Hysteresis
GG
8532
Float
4
R W Percent 0 - 100
AEM 4 Protection 8
Arming Delay
GG
8534
Float
4
R W Second 0 - 300
AEM 4 Protection 8
Threshold 1 Pickup
GG
8536
Float
4
R W n/a
-999999 - 999999
AEM 4 Protection 8
Threshold 1 Activation Delay GG
8538
Float
4
R W Second 0 - 300
AEM 4 Protection 8
Threshold 1 Alarm
Configuration
GG
8540
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 8
Threshold 2 Pickup
GG
8542
Float
4
R W n/a
-999999 - 999999
AEM 4 Protection 8
Threshold 2 Activation Delay GG
8544
Float
4
R W Second 0 - 300
AEM 4 Protection 8
Threshold 2 Alarm
Configuration
GG
8546
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 8
Threshold 3 Pickup
GG
8548
Float
4
R W n/a
-999999 - 999999
AEM 4 Protection 8
Threshold 3 Activation Delay GG
8550
Float
4
R W Second 0 - 300
AEM 4 Protection 8
Threshold 3 Alarm
Configuration
GG
8552
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 8
Threshold 4 Pickup
GG
8554
Float
4
R W n/a
-999999 - 999999
AEM 4 Protection 8
Threshold 4 Activation Delay GG
8556
Float
4
R W Second 0 - 300
AEM 4 Protection 8
Threshold 4 Alarm
Configuration
GG
8558
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Remote Analog
Output 1
Parameter Selection
GG
8560
Int32
4
R W n/a
No Parameter=0
Oil Pressure=1
Coolant Temp=2
Battery Volts=3
RPM=4
Fuel Level=5
Gen Hz=6
Gen VAB=7
Gen VBC=8
Gen VCA=9
Gen Vavg LL=10
Gen VAN=11
Gen VBN=12
Gen VCN=13
Gen Vavg LN=14
Bus 1 Hz=15
Bus 1 VAB=16
Bus 1 VBC=17
Bus 1 VCA=18
Bus 1 Vavg LL=19
Bus 1 VA=20
Bus 1 VB=21
Bus 1 VC=22
Bus 1 Vavg LN=23
Bus 2 Hz=24
Bus 2 VAB=25
Bus 2 VBC=26