Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 194
188
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group Register Type Bytes R/W
Unit
Range
51-4
Mode
SG1 3P 23852
Uint32 4
R W n/a
Disabled=0
IA=1
IB=2
IC=3
Imax=4
3I0=5
I2=6
IG=7
I1=8
51-4
Source
SG1 3P 23854
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-4
Pickup
SG1 3P 23856
Float
4
R W Amp
0.9 - 7.75
51-4
Curve Index
SG1 3P 23858
Uint32 4
R W n/a
S1=0
S2=1
L1=2
L2=3
D=4
M=5
I1=6
I2=7
V1=8
V2=9
E1=10
E2=11
A=12
B=13
C=14
G=15
F=16
46=17
P=18
51-4
Direction
SG1 3P 23860
Uint32 4
R W n/a
Forward=0
Reverse=1
Non-Directional=2
51-4
Use Instantaneous Reset
SG1 3P 23862
Uint32 4
R W n/a
Integrating=0
Instantaneous=1
51-4
Constant TD
SG1 3P 23864
Float
4
R W n/a
0 - 9.9
51-4
Constant A
SG1 3P 23866
Float
4
R W n/a
0 - 600
51-4
Constant B
SG1 3P 23868
Float
4
R W n/a
0 - 25
51-4
Constant C
SG1 3P 23870
Float
4
R W n/a
0 - 1
51-4
Constant N
SG1 3P 23872
Float
4
R W n/a
0.5 - 2.5
51-4
Constant R
SG1 3P 23874
Float
4
R W n/a
0 - 30
51-4
Voltage Restraint Setpoint
SG1 3P 23876
Float
4
R W Volt
30 - 250
51-4
Voltage Restraint Mode
SG1 3P 23878
Uint32 4
R W n/a
Disabled=0
Control=1
Restraint=2
51-4
Alarm Configuration
SG1 3P 23880
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
51-4
Low-Line Scale
SG1 3P 23882
Float
4
R W n/a
0.001 - 3
51-4
Voltage Restraint Source
SG1 3P 23884
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-4
Constant Q
SG1 3P 23886
Float
4
R W n/a
0.1 - 10
51-4
Mode
SG2 1P 23888
Uint32 4
R W n/a
Disabled=0
IA=1
IB=2
IC=3
Imax=4
3I0=5
I2=6
IG=7
I1=8
51-4
Source
SG2 1P 23890
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-4
Pickup
SG2 1P 23892
Float
4
R W Amp
0.9 - 7.75