Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 116

110
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group Register Type Bytes R/W
Unit
Range
AEM 4 Input Config. 5
Alarm Config
GG
8292
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Input Config. 6
Parameter Minimum
GG
8294
Float
4
R W n/a
-999999 - 999999
AEM 4 Input Config. 6
Parameter Maximum
GG
8296
Float
4
R W n/a
-999999 - 999999
AEM 4 Input Config. 6
Current Minimum
GG
8298
Float
4
R W Milliamp 4 - 20
AEM 4 Input Config. 6
Current Maximum
GG
8300
Float
4
R W Milliamp 4 - 20
AEM 4 Input Config. 6
Voltage Minimum
GG
8302
Float
4
R W Volt
0 - 10
AEM 4 Input Config. 6
Voltage Maximum
GG
8304
Float
4
R W Volt
0 - 10
AEM 4 Input Config. 6
Alarm Configuration
GG
8306
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Input Config. 7
Parameter Minimum
GG
8308
Float
4
R W n/a
-999999 - 999999
AEM 4 Input Config. 7
Parameter Maximum
GG
8310
Float
4
R W n/a
-999999 - 999999
AEM 4 Input Config. 7
Current Minimum
GG
8312
Float
4
R W Milliamp 4 - 20
AEM 4 Input Config. 7
Current Maximum
GG
8314
Float
4
R W Milliamp 4 - 20
AEM 4 Input Config. 7
Voltage Minimum
GG
8316
Float
4
R W Volt
0 - 10
AEM 4 Input Config. 7
Voltage Maximum
GG
8318
Float
4
R W Volt
0 - 10
AEM 4 Input Config. 7
Alarm Configuration
GG
8320
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Input Config. 8
Parameter Minimum
GG
8322
Float
4
R W n/a
-999999 - 999999
AEM 4 Input Config. 8
Parameter Maximum
GG
8324
Float
4
R W n/a
-999999 - 999999
AEM 4 Input Config. 8
Current Minimum
GG
8326
Float
4
R W Milliamp 4 - 20
AEM 4 Input Config. 8
Current Maximum
GG
8328
Float
4
R W Milliamp 4 - 20
AEM 4 Input Config. 8
Voltage Minimum
GG
8330
Float
4
R W Volt
0 - 10
AEM 4 Input Config. 8
Voltage Maximum
GG
8332
Float
4
R W Volt
0 - 10
AEM 4 Input Config. 8
Alarm Configuration
GG
8334
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 1
Hysteresis
GG
8336
Float
4
R W Percent 0 - 100
AEM 4 Protection 1
Arming Delay
GG
8338
Float
4
R W Second 0 - 300
AEM 4 Protection 1
Threshold 1 Pickup
GG
8340
Float
4
R W n/a
-999999 - 999999
AEM 4 Protection 1
Threshold 1 Activation Delay GG
8342
Float
4
R W Second 0 - 300
AEM 4 Protection 1
Threshold 1 Alarm
Configuration
GG
8344
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 1
Threshold 2 Pickup
GG
8346
Float
4
R W n/a
-999999 - 999999
AEM 4 Protection 1
Threshold 2 Activation Delay GG
8348
Float
4
R W Second 0 - 300
AEM 4 Protection 1
Threshold 2 Alarm
Configuration
GG
8350
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 1
Threshold 3 Pickup
GG
8352
Float
4
R W n/a
-999999 - 999999
AEM 4 Protection 1
Threshold 3 Activation Delay GG
8354
Float
4
R W Second 0 - 300
AEM 4 Protection 1
Threshold 3 Alarm
Configuration
GG
8356
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 1
Threshold 4 Pickup
GG
8358
Float
4
R W n/a
-999999 - 999999
AEM 4 Protection 1
Threshold 4 Activation Delay GG
8360
Float
4
R W Second 0 - 300
AEM 4 Protection 1
Threshold 4 Alarm
Configuration
GG
8362
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 2
Hysteresis
GG
8364
Float
4
R W Percent 0 - 100
AEM 4 Protection 2
Arming Delay
GG
8366
Float
4
R W Second 0 - 300
AEM 4 Protection 2
Threshold 1 Pickup
GG
8368
Float
4
R W n/a
-999999 - 999999
AEM 4 Protection 2
Threshold 1 Activation Delay GG
8370
Float
4
R W Second 0 - 300
AEM 4 Protection 2
Threshold 1 Alarm
Configuration
GG
8372
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 2
Threshold 2 Pickup
GG
8374
Float
4
R W n/a
-999999 - 999999
AEM 4 Protection 2
Threshold 2 Activation Delay GG
8376
Float
4
R W Second 0 - 300
AEM 4 Protection 2
Threshold 2 Alarm
Configuration
GG
8378
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 2
Threshold 3 Pickup
GG
8380
Float
4
R W n/a
-999999 - 999999
AEM 4 Protection 2
Threshold 3 Activation Delay GG
8382
Float
4
R W Second 0 - 300
AEM 4 Protection 2
Threshold 3 Alarm
Configuration
GG
8384
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 2
Threshold 4 Pickup
GG
8386
Float
4
R W n/a
-999999 - 999999
AEM 4 Protection 2
Threshold 4 Activation Delay GG
8388
Float
4
R W Second 0 - 300
AEM 4 Protection 2
Threshold 4 Alarm
Configuration
GG
8390
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
AEM 4 Protection 3
Hysteresis
GG
8392
Float
4
R W Percent 0 - 100
AEM 4 Protection 3
Arming Delay
GG
8394
Float
4
R W Second 0 - 300
AEM 4 Protection 3
Threshold 1 Pickup
GG
8396
Float
4
R W n/a
-999999 - 999999