Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 207
9469300991 Rev A
201
DGC-2020HD Modbus
™ Protocol
Default Register Table
Name
Description
Group Register Type Bytes R/W
Unit
Range
51-6
Curve Index
SG2 1P 24470
Uint32 4
R W n/a
S1=0
S2=1
L1=2
L2=3
D=4
M=5
I1=6
I2=7
V1=8
V2=9
E1=10
E2=11
A=12
B=13
C=14
G=15
F=16
46=17
P=18
51-6
Direction
SG2 1P 24472
Uint32 4
R W n/a
Forward=0
Reverse=1
Non-Directional=2
51-6
Use Instantaneous Reset
SG2 1P 24474
Uint32 4
R W n/a
Integrating=0
Instantaneous=1
51-6
Constant TD
SG2 1P 24476
Float
4
R W n/a
0 - 9.9
51-6
Constant A
SG2 1P 24478
Float
4
R W n/a
0 - 600
51-6
Constant B
SG2 1P 24480
Float
4
R W n/a
0 - 25
51-6
Constant C
SG2 1P 24482
Float
4
R W n/a
0 - 1
51-6
Constant N
SG2 1P 24484
Float
4
R W n/a
0.5 - 2.5
51-6
Constant R
SG2 1P 24486
Float
4
R W n/a
0 - 30
51-6
Voltage Restraint Setpoint
SG2 1P 24488
Float
4
R W Volt
30 - 250
51-6
Voltage Restraint Mode
SG2 1P 24490
Uint32 4
R W n/a
Disabled=0
Control=1
Restraint=2
51-6
Alarm Configuration
SG2 1P 24492
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
51-6
Low-Line Scale
SG2 1P 24494
Float
4
R W n/a
0.001 - 3
51-6
Voltage Restraint Source
SG2 1P 24496
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-6
Constant Q
SG2 1P 24498
Float
4
R W n/a
0.1 - 10
51-6
Mode
SG2 3P 24500
Uint32 4
R W n/a
Disabled=0
IA=1
IB=2
IC=3
Imax=4
3I0=5
I2=6
IG=7
I1=8
51-6
Source
SG2 3P 24502
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-6
Pickup
SG2 3P 24504
Float
4
R W Amp
0.9 - 7.75
51-6
Curve Index
SG2 3P 24506
Uint32 4
R W n/a
S1=0
S2=1
L1=2
L2=3
D=4
M=5
I1=6
I2=7
V1=8
V2=9
E1=10
E2=11
A=12
B=13
C=14
G=15
F=16
46=17
P=18
51-6
Direction
SG2 3P 24508
Uint32 4
R W n/a
Forward=0
Reverse=1
Non-Directional=2
51-6
Use Instantaneous Reset
SG2 3P 24510
Uint32 4
R W n/a
Integrating=0
Instantaneous=1
51-6
Constant TD
SG2 3P 24512
Float
4
R W n/a
0 - 9.9