Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 50
44
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Register Bit Type Bytes R/W
Range
Genset Controller
Start Delay Bypass
1106
5
Uint16 2
R
False=0 True=1
Genset Controller
Overcrank Alarm
1106
6
Uint16 2
R
False=0 True=1
Genset Controller
Off Mode Cooldown
1106
7
Uint16 2
R
False=0 True=1
Genset Controller
Cooldown and Stop Request From Logic
1106
8
Uint16 2
R
False=0 True=1
Genset Controller
Cooldown Request From Logic
1106
9
Uint16 2
R
False=0 True=1
Genset Controller
In Unloading State
1106
10 Uint16 2
R
False=0 True=1
Genset Controller
Auto Mode Status
1106
11 Uint16 2
R
False=0 True=1
Genset Controller
Off Mode Status
1106
12 Uint16 2
R
False=0 True=1
Genset Controller
Run Mode Status
1106
13 Uint16 2
R
False=0 True=1
Genset Controller
Paralleled to Mains
1106
14 Uint16 2
R
False=0 True=1
Genset Controller
Emergency Stop Button
1106
15 Uint16 2
R
False=0 True=1
Genset Controller
Cooldown Timer Active
1107
0
Uint16 2
R
False=0 True=1
Genset Controller
Idle Request Active
1107
1
Uint16 2
R
False=0 True=1
Genset Controller
Low Coolant Pre-Alarm Global
1107
2
Uint16 2
R
False=0 True=1
Genset Controller
Low Coolant Alarm Global
1107
3
Uint16 2
R
False=0 True=1
Genset Controller
Low Coolant Status Global
1107
4
Uint16 2
R
False=0 True=1
Coms Control Group
Reset Active
1107
5
Uint16 2
R
False=0 True=1
Coms Control Group
Lamp Test Active
1107
6
Uint16 2
R
False=0 True=1
Load Detection
Supplying Load
1107
7
Uint16 2
R
False=0 True=1
Run Statistics
Maintenance Due
1107
8
Uint16 2
R
False=0 True=1
Unit ID Table
ID Missing Pre-Alarm
1107
9
Uint16 2
R
False=0 True=1
Unit ID Table
ID Repeat Pre-Alarm
1107
10 Uint16 2
R
False=0 True=1
Load Share Settings
Intergenset Comms Fail
1107
11 Uint16 2
R
False=0 True=1
Auto Restart
Auto Restart Fail Alarm
1107
12 Uint16 2
R
False=0 True=1
ECU Config
Loss of ECU Comm Alarm
1107
13 Uint16 2
R
False=0 True=1
ECU Config
Loss of ECU Comm Pre-Aalarm
1107
14 Uint16 2
R
False=0 True=1
ECU Config
Diagnostic Trouble Code Pre-Alarm
1107
15 Uint16 2
R
False=0 True=1
ECU Config
Shutdown
1108
0
Uint16 2
R
False=0 True=1
ECU Config
DEF Empty
1108
1
Uint16 2
R
False=0 True=1
ECU Config
DEF Engine Derate
1108
2
Uint16 2
R
False=0 True=1
ECU Config
DEF Inducement Override
1108
3
Uint16 2
R
False=0 True=1
ECU Config
DEF Low
1108
4
Uint16 2
R
False=0 True=1
ECU Config
DEF Presevere Inducement
1108
5
Uint16 2
R
False=0 True=1
ECU Config
DEF Severe Inducement
1108
6
Uint16 2
R
False=0 True=1
ECU Config
DPF Regenerate Disabled
1108
7
Uint16 2
R
False=0 True=1
ECU Config
DPF Regenerate Required
1108
8
Uint16 2
R
False=0 True=1
ECU Config
DPF Soot Level High Least Severe
1108
9
Uint16 2
R
False=0 True=1
ECU Config
DPF Soot Level High Moderately Severe
1108
10 Uint16 2
R
False=0 True=1
ECU Config
DPF Soot Level High Most Severe
1108
11 Uint16 2
R
False=0 True=1
ECU Config
Fuel Filter 1 Leak
1108
12 Uint16 2
R
False=0 True=1
ECU Config
Fuel Filter 2 Leak
1108
13 Uint16 2
R
False=0 True=1
ECU Config
High Exhaust Temp
1108
14 Uint16 2
R
False=0 True=1
ECU Config
Low Coolant Level Alarm From DTC
1108
15 Uint16 2
R
False=0 True=1
ECU Config
MTU High Charge Air Temp Alarm
1109
0
Uint16 2
R
False=0 True=1
ECU Config
MTU High Oil Temp Alarm
1109
1
Uint16 2
R
False=0 True=1
ECU Config
MTU High Coolant Temp Alarm
1109
2
Uint16 2
R
False=0 True=1
ECU Config
MTU Low Aftercooler Cool LVL Alarm
1109
3
Uint16 2
R
False=0 True=1
ECU Config
MTU Low Fuel Delivery Pressure Alarm
1109
4
Uint16 2
R
False=0 True=1
ECU Config
MTU Low Oil Pressure Alarm
1109
5
Uint16 2
R
False=0 True=1
ECU Config
MTU Overspeed Alarm
1109
6
Uint16 2
R
False=0 True=1
ECU Config
MTU Combined Red Alarm Status From ECU
1109
7
Uint16 2
R
False=0 True=1
ECU Config
MTU High ECU Temp Pre-Alarm
1109
8
Uint16 2
R
False=0 True=1
ECU Config
MTU High Oil Temp Pre-Alarm
1109
9
Uint16 2
R
False=0 True=1
ECU Config
MTU High Intercooler Temp Pre-Alarm
1109
10 Uint16 2
R
False=0 True=1
ECU Config
MTU High Charge Air Temp Pre-Alarm
1109
11 Uint16 2
R
False=0 True=1
ECU Config
MTU High Coolant Temp Pre-Alarm
1109
12 Uint16 2
R
False=0 True=1
ECU Config
MTU Shutdown Override Pre-Alarm
1109
13 Uint16 2
R
False=0 True=1
ECU Config
MTU High Fuel Rail Pressure Pre-Alarm
1109
14 Uint16 2
R
False=0 True=1
ECU Config
MTU Low Fuel Rail Pressure Pre-Alarm
1109
15 Uint16 2
R
False=0 True=1
ECU Config
MTU Low Coolant Level Pre-Alarm
1110
0
Uint16 2
R
False=0 True=1
ECU Config
MTU Low Charge Air Pressure Pre-Alarm
1110
1
Uint16 2
R
False=0 True=1
ECU Config
MTU Low Fuel Delivery Pressure Pre-Alarm
1110
2
Uint16 2
R
False=0 True=1
ECU Config
MTU Low Oil Pressure Pre-Alarm
1110
3
Uint16 2
R
False=0 True=1
ECU Config
MTU Combined Yellow Pre-Alarm
1110
4
Uint16 2
R
False=0 True=1
ECU Config
MTU Hi Fuel Filter Diff Pressure Pre-Alarm
1110
5
Uint16 2
R
False=0 True=1
ECU Config
MTU Test Overspeed Active Pre-Alarm
1110
6
Uint16 2
R
False=0 True=1
ECU Config
CAN Mode Feedback Status
1110
7
Uint16 2
R
False=0 True=1
ECU Config
Cylinder Cutout Status
1110
8
Uint16 2
R
False=0 True=1
ECU Config
ECU Faulty Pre-Alarm
1110
9
Uint16 2
R
False=0 True=1
ECU Config
ECU Override Feedback Status
1110
10 Uint16 2
R
False=0 True=1
ECU Config
Engine Running Status Bit
1110
11 Uint16 2
R
False=0 True=1
ECU Config
Engine Speed Too Low Pre-Alarm
1110
12 Uint16 2
R
False=0 True=1
ECU Config
External Stop Active Status
1110
13 Uint16 2
R
False=0 True=1
ECU Config
Hi Day Tank Level Pre-Alarm
1110
14 Uint16 2
R
False=0 True=1
ECU Config
High ECU Supply Voltage Alarm
1110
15 Uint16 2
R
False=0 True=1