249
DGC-2020HD Modbus
™ Protocol
Legacy Register Table
Register
Description
Type
Units
Scaling
Factor
R/W
Range
44832-33
Status Metering 1
Int32
n/a
n/a
R
Bit 0 = Idle Request
Bit 1 = Lamp Test
Bit 2 = Alarm Silence
Bit 3 = Reset
Bit 4 = Alternate Frequency Override
Bit 5 = Start Delay Bypass
Bit 6 = Cooldown and Stop Request
from Logic
Bit 7 = Cooldown Request from Logic
Bit 8 = External Start Delay
Bit 9 = Off Mode Cooldown
Bit 10 = PF Mode Active
Bit 11 = Var Mode Active
Bit 12 = Cooldown Timer Active
Bit 13 = Engine Running
Bit 14 = Fuel Leak Detect
Bit 15 = Battery Charger Failure
Bit 16 = Low Coolant Level
Bit 17 = Gen Failed
Bit 18 = Gen Stable
Bit 19 = Gen Dead
Bit 20 = Bus Failed
Bit 21 = Bus Stable
Bit 22 = Bus Dead
Bit 23 = Gen Breaker Closed
Bit 24 = Mains Breaker Closed
Bit 25 = Grounded Delta Override
Bit 26 = Battle Override
Bit 27 = Auto Transfer Switch
Bit 28 = Low Line Override
Bit 29 = Single-Phase AC Override
Bit 30 = Single-Phase Override
Bit 31 = EPS Supplying Load
44834
Hours Until Maintenance
Int32
n/a
n/a
RW 0 - 5000
44836
Cum. Total Engine Run Hrs.
Int32
Hour
n/a
R
0 - 99999
44838
Cum. Total Engine Run Min.
Int32
n/a
n/a
R
0 - 59
44840
Cum. Loaded Engine Run Hrs.
Int32
n/a
n/a
R
0 - 99999
44842
Cum. Loaded Engine Run Min.
Int32
n/a
n/a
R
0 - 59
44844
Cum. Unloaded Engine Run Hrs.
Int32
Hour
n/a
R
0 - 99999
44846
Cum. Unloaded Engine Run Min.
Int32
n/a
n/a
R
0 - 59
44848
Cum. Total kW-Hrs
Uint32 kilowatt-
hour
n/a
R
0 - 999999999
44850
Reserved
44852
Commission Date Month
Uint32 n/a
n/a
RW 1 - 12
44854
Commission Date Day
Uint32 n/a
n/a
RW 1 - 31
44856
Commission Date Year
Uint32 n/a
n/a
RW 0 - 99
44858
Session Total Engine Run Hrs.
Int32
Hour
n/a
R
0 - 99999
44860
Session Total Engine Run Min.
Int32
n/a
n/a
R
0 - 59
44862
Session Loaded Engine Run Hrs.
Int32
Hour
n/a
R
0 - 99999
44864
Session Loaded Engine Run Min.
Int32
n/a
n/a
R
0 - 59
44866
Session Unloaded Engine Run Hrs.
Int32
Hour
n/a
R
0 - 99999
44868
Session Unloaded Engine Run Min.
Int32
n/a
n/a
R
0 - 59
44870
Session kW-Hrs
Int32
kilowatt-
hour
n/a
R
0 - 999999999
44872
Cumulative Number of Engine Starts
Uint32 n/a
n/a
RW 0 - 65535
44874
Session Start Date Month
Uint32 n/a
n/a
RW 1 - 12
44876
Session Start Date Day
Uint32 n/a
n/a
RW 1 - 31
44878
Session Start Date Year
Uint32 n/a
n/a
RW 0 - 99
44880
Generator Status
Uint32 n/a
n/a
R
0 = RESET State
1 = READY State
2 = CRANKING State
3 = RESTING State
4 = RUNNING State
5 = ALARM State
6 = PRESTART State
7 = COOLING State
8 = CONNECTING State
9 = DISCONNECT State
10 = PULSING State
11 = UNLOADING State
44882-932
Reserved