Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 182
176
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group Register Type Bytes R/W
Unit
Range
51-2
Mode
SG1 3P 23276
Uint32 4
R W n/a
Disabled=0
IA=1
IB=2
IC=3
Imax=4
3I0=5
I2=6
IG=7
I1=8
51-2
Source
SG1 3P 23278
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-2
Pickup
SG1 3P 23280
Float
4
R W Amp
0.9 - 7.75
51-2
Curve Index
SG1 3P 23282
Uint32 4
R W n/a
S1=0
S2=1
L1=2
L2=3
D=4
M=5
I1=6
I2=7
V1=8
V2=9
E1=10
E2=11
A=12
B=13
C=14
G=15
F=16
46=17
P=18
51-2
Direction
SG1 3P 23284
Uint32 4
R W n/a
Forward=0
Reverse=1
Non-Directional=2
51-2
Use Instantaneous Reset
SG1 3P 23286
Uint32 4
R W n/a
Integrating=0
Instantaneous=1
51-2
Constant TD
SG1 3P 23288
Float
4
R W n/a
0 - 9.9
51-2
Constant A
SG1 3P 23290
Float
4
R W n/a
0 - 600
51-2
Constant B
SG1 3P 23292
Float
4
R W n/a
0 - 25
51-2
Constant C
SG1 3P 23294
Float
4
R W n/a
0 - 1
51-2
Constant N
SG1 3P 23296
Float
4
R W n/a
0.5 - 2.5
51-2
Constant R
SG1 3P 23298
Float
4
R W n/a
0 - 30
51-2
Voltage Restraint Setpoint
SG1 3P 23300
Float
4
R W Volt
30 - 250
51-2
Voltage Restraint Mode
SG1 3P 23302
Uint32 4
R W n/a
Disabled=0
Control=1
Restraint=2
51-2
Alarm Configuration
SG1 3P 23304
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
51-2
Low-Line Scale
SG1 3P 23306
Float
4
R W n/a
0.001 - 3
51-2
Voltage Restraint Source
SG1 3P 23308
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-2
Constant Q
SG1 3P 23310
Float
4
R W n/a
0.1 - 10
51-2
Mode
SG2 1P 23312
Uint32 4
R W n/a
Disabled=0
IA=1
IB=2
IC=3
Imax=4
3I0=5
I2=6
IG=7
I1=8
51-2
Source
SG2 1P 23314
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-2
Pickup
SG2 1P 23316
Float
4
R W Amp
0.9 - 7.75