Default Register Table
Name
Description
Group Register Type Bytes R/W
Unit
Range
AEM 4 RTD Input 4=365
AEM 4 RTD Input 5=366
AEM 4 RTD Input 6=367
AEM 4 RTD Input 7=368
AEM 4 RTD Input 8=369
AEM 4 TC Input 1=370
AEM 4 TC Input 2=371
AVR Output=372
GOV Output=373
LS Output=374
Config Protection 5
Hysteresis
GG
24938
Float
4
R W Percent
0 - 100
Config Protection 5
Arming Delay
GG
24940
Float
4
R W Second
0 - 300
Config Protection 5
Threshold 1 Type
GG
24942
Int32
4
R W n/a
Disabled=0
Over=1
Under=2
Config Protection 5
Threshold 1 Pickup
GG
24944
Float
4
R W n/a
-999999 - 999999
Config Protection 5
Threshold 1 Activation Delay
GG
24946
Float
4
R W Second
0 - 300
Config Protection 5
Threshold 1 Alarm Configuration GG
24948
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Protection 5
Threshold 2 Type
GG
24950
Int32
4
R W n/a
Disabled=0
Over=1
Under=2
Config Protection 5
Threshold 2 Pickup
GG
24958
Float
4
R W n/a
-999999 - 999999
Config Protection 5
Threshold 2 Activation Delay
GG
24960
Float
4
R W Second
0 - 300
Config Protection 5
Threshold 2 Alarm Configuration GG
24962
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Protection 5
Threshold 3 Type
GG
24964
Int32
4
R W n/a
Disabled=0
Over=1
Under=2
Config Protection 5
Threshold 3 Pickup
GG
24966
Float
4
R W n/a
-999999 - 999999
Config Protection 5
Threshold 3 Activation Delay
GG
24968
Float
4
R W Second
0 - 300
Config Protection 5
Threshold 3 Alarm Configuration GG
24970
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Protection 5
Threshold 4 Type
GG
24972
Int32
4
R W n/a
Disabled=0
Over=1
Under=2
Config Protection 5
Threshold 4 Pickup
GG
24974
Float
4
R W n/a
-999999 - 999999
Config Protection 5
Threshold 4 Activation Delay
GG
24976
Float
4
R W Second
0 - 300
Config Protection 5
Threshold 4 Alarm Configuration GG
24978
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Protection 5
Low-Line Scale Current
GG
24980
Float
4
R W n/a
0.001 - 3
Config Protection 5
Low-Line Scale Voltage
GG
24982
Float
4
R W n/a
0.001 - 3
Config Protection 5
Label
GG
24984
String 16
R W n/a
0 - 16
Config Protection 6
Parameter Selection
GG
24986
Int32
4
R W n/a
No Parameter=0
Oil Pressure=1
Coolant Temp=2
Battery Volts=3
RPM=4
Fuel Level=5
Gen Hz=6
Gen VAB=7
Gen VBC=8
Gen VCA=9
Gen Vavg LL=10
Gen VAN=11
Gen VBN=12
Gen VCN=13
Gen Vavg LN=14
Bus 1 Hz=15
Bus 1 VAB=16
Bus 1 VBC=17
Bus 1 VCA=18
Bus 1 Vavg LL=19
Bus 1 VA=20
Bus 1 VB=21
Bus 1 VC=22
Bus 1 Vavg LN=23
Bus 2 Hz=24
Bus 2 VAB=25
Bus 2 VBC=26
Bus 2 VCA=27
Bus 2 Vavg LL=28
Bus 2 VAN=29
Bus 2 VBN=30
Bus 2 VCN=31
Bus 2 Vavg LN=32