Protection settings – Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 139
![background image](https://www.manualsdir.com/files/773959/content/doc139.png)
9469300991 Rev A
133
DGC-2020HD Modbus
™ Protocol
Default Register Table
Name
Description
Group Register Type Bytes R/W
Unit
Range
AEM 4 Metering
RTD Input 2 Raw Value
GG
10876
Float
4
R
Ohm
n/a
AEM 4 Metering
RTD Input 3 Raw Value
GG
10878
Float
4
R
Ohm
n/a
AEM 4 Metering
RTD Input 4 Raw Value
GG
10880
Float
4
R
Ohm
n/a
AEM 4 Metering
RTD Input 5 Raw Value
GG
10882
Float
4
R
Ohm
n/a
AEM 4 Metering
RTD Input 6 Raw Value
GG
10884
Float
4
R
Ohm
n/a
AEM 4 Metering
RTD Input 7 Raw Value
GG
10886
Float
4
R
Ohm
n/a
AEM 4 Metering
RTD Input 8 Raw Value
GG
10888
Float
4
R
Ohm
n/a
AEM 4 Metering
RTD Input 1 Scaled
Value
GG
10890
Float
4
R
Deg F
n/a
AEM 4 Metering
RTD Input 2 Scaled
Value
GG
10892
Float
4
R
Deg F
n/a
AEM 4 Metering
RTD Input 3 Scaled
Value
GG
10894
Float
4
R
Deg F
n/a
AEM 4 Metering
RTD Input 4 Scaled
Value
GG
10896
Float
4
R
Deg F
n/a
AEM 4 Metering
RTD Input 5 Scaled
Value
GG
10898
Float
4
R
Deg F
n/a
AEM 4 Metering
RTD Input 6 Scaled
Value
GG
10900
Float
4
R
Deg F
n/a
AEM 4 Metering
RTD Input 7 Scaled
Value
GG
10902
Float
4
R
Deg F
n/a
AEM 4 Metering
RTD Input 8 Scaled
Value
GG
10904
Float
4
R
Deg F
n/a
AEM 4 Metering
Thermal Input 1 Raw
Value
GG
10906
Float
4
R
Millivolt
n/a
AEM 4 Metering
Thermal Input 2 Raw
Value
GG
10908
Float
4
R
Millivolt
n/a
AEM 4 Metering
Analog Output 1 Raw
Value
GG
10910
Float
4
R
n/a
n/a
AEM 4 Metering
Analog Output 2 Raw
Value
GG
10912
Float
4
R
n/a
n/a
AEM 4 Metering
Analog Output 3 Raw
Value
GG
10914
Float
4
R
n/a
n/a
AEM 4 Metering
Analog Output 4 Raw
Value
GG
10916
Float
4
R
n/a
n/a
AEM 4 Metering
Analog Output 1 Scaled
Value
GG
10918
Float
4
R
n/a
n/a
AEM 4 Metering
Analog Output 2 Scaled
Value
GG
10920
Float
4
R
n/a
n/a
AEM 4 Metering
Analog Output 3 Scaled
Value
GG
10922
Float
4
R
n/a
n/a
AEM 4 Metering
Analog Output 4 Scaled
Value
GG
10924
Float
4
R
n/a
n/a
AEM 4 Metering
Thermal Input 1 Scaled
Value
GG
10926
Float
4
R
Deg F
n/a
AEM 4 Metering
Thermal Input 2 Scaled
Value
GG
10928
Float
4
R
Deg F
n/a
Protection Settings
Name
Description
Group Register Type Bytes R/W
Unit
Range
27P-1
Mode
SG0 1P 20000
Uint32 4
R W n/a
Disabled=0
Enabled=1
27P-1
Source
SG0 1P 20002
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
27P-1
Pickup
SG0 1P 20004
Float
4
R W Volt
1 - 576
27P-1
Time Delay
SG0 1P 20006
Float
4
R W Millisecond 0 - 600000
27P-1
Alarm Configuration
SG0 1P 20008
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
27P-1
Low-Line Scale
SG0 1P 20010
Float
4
R W n/a
0.001 - 3
27P-1
Frequency Inhibit
SG0 1P 20012
Float
4
R W Hertz
20 - 90
27P-1
Mode
SG0 3P 20014
Uint32 4
R W n/a
Disabled=0
Enabled=1
27P-1
Source
SG0 3P 20016
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
27P-1
Pickup
SG0 3P 20018
Float
4
R W Volt
1 - 576
27P-1
Time Delay
SG0 3P 20020
Float
4
R W Millisecond 0 - 600000
27P-1
Alarm Configuration
SG0 3P 20022
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
27P-1
Low-Line Scale
SG0 3P 20024
Float
4
R W n/a
0.001 - 3
27P-1
Frequency Inhibit
SG0 3P 20026
Float
4
R W Hertz
20 - 90