156
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group Register Type Bytes R/W
Unit
Range
81-8
Source
SG2
21898
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
81-8
Pickup
SG2
21900
Float
4
R W Hertz
37.5 - 66
81-8
Time Delay
SG2
21902
Float
4
R W Millisecond 0 - 600000
81-8
Voltage Inhibit
SG2
21904
Float
4
R W Percent
1 - 100
81-8
Alarm Configuration
SG2
21906
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
81-8
Mode
SG3
21908
Uint32 4
R W n/a
Disabled=0
Over=1
Under=2
81-8
Source
SG3
21910
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
81-8
Pickup
SG3
21912
Float
4
R W Hertz
37.5 - 66
81-8
Time Delay
SG3
21914
Float
4
R W Millisecond 0 - 600000
81-8
Voltage Inhibit
SG3
21916
Float
4
R W Percent
1 - 100
81-8
Alarm Configuration
SG3
21918
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
40Q-1
Mode
SG0 1P 21920
Uint32 4
R W n/a
Disabled=0
Enabled=1
40Q-1
Pickup
SG0 1P 21922
Float
4
R W Percent
-150 - 0
40Q-1
Time Delay
SG0 1P 21924
Float
4
R W Millisecond 0 - 600000
40Q-1
Source
SG0 1P 21926
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
40Q-1
Alarm Configuration
SG0 1P 21928
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
40Q-1
Low-Line Scale
SG0 1P 21930
Float
4
R W n/a
0.001 - 3
40Q-1
Mode
SG0 3P 21932
Uint32 4
R W n/a
Disabled=0
Enabled=1
40Q-1
Pickup
SG0 3P 21934
Float
4
R W Percent
-150 - 0
40Q-1
Time Delay
SG0 3P 21936
Float
4
R W Millisecond 0 - 600000
40Q-1
Source
SG0 3P 21938
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
40Q-1
Alarm Configuration
SG0 3P 21940
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
40Q-1
Low-Line Scale
SG0 3P 21942
Float
4
R W n/a
0.001 - 3
40Q-1
Mode
SG1 1P 21944
Uint32 4
R W n/a
Disabled=0
Enabled=1
40Q-1
Pickup
SG1 1P 21946
Float
4
R W Percent
-150 - 0
40Q-1
Time Delay
SG1 1P 21948
Float
4
R W Millisecond 0 - 600000
40Q-1
Source
SG1 1P 21950
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
40Q-1
Alarm Configuration
SG1 1P 21952
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
40Q-1
Low-Line Scale
SG1 1P 21954
Float
4
R W n/a
0.001 - 3
40Q-1
Mode
SG1 3P 21956
Uint32 4
R W n/a
Disabled=0
Enabled=1
40Q-1
Pickup
SG1 3P 21958
Float
4
R W Percent
-150 - 0
40Q-1
Time Delay
SG1 3P 21960
Float
4
R W Millisecond 0 - 600000
40Q-1
Source
SG1 3P 21962
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
40Q-1
Alarm Configuration
SG1 3P 21964
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
40Q-1
Low-Line Scale
SG1 3P 21966
Float
4
R W n/a
0.001 - 3
40Q-1
Mode
SG2 1P 21968
Uint32 4
R W n/a
Disabled=0
Enabled=1
40Q-1
Pickup
SG2 1P 21970
Float
4
R W Percent
-150 - 0
40Q-1
Time Delay
SG2 1P 21972
Float
4
R W Millisecond 0 - 600000
40Q-1
Source
SG2 1P 21974
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
40Q-1
Alarm Configuration
SG2 1P 21976
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
40Q-1
Low-Line Scale
SG2 1P 21978
Float
4
R W n/a
0.001 - 3
40Q-1
Mode
SG2 3P 21980
Uint32 4
R W n/a
Disabled=0
Enabled=1