Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 200

194
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group Register Type Bytes R/W
Unit
Range
51-5
Mode
SG1 3P 24140
Uint32 4
R W n/a
Disabled=0
IA=1
IB=2
IC=3
Imax=4
3I0=5
I2=6
IG=7
I1=8
51-5
Source
SG1 3P 24142
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-5
Pickup
SG1 3P 24144
Float
4
R W Amp
0.9 - 7.75
51-5
Curve Index
SG1 3P 24146
Uint32 4
R W n/a
S1=0
S2=1
L1=2
L2=3
D=4
M=5
I1=6
I2=7
V1=8
V2=9
E1=10
E2=11
A=12
B=13
C=14
G=15
F=16
46=17
P=18
51-5
Direction
SG1 3P 24148
Uint32 4
R W n/a
Forward=0
Reverse=1
Non-Directional=2
51-5
Use Instantaneous Reset
SG1 3P 24150
Uint32 4
R W n/a
Integrating=0
Instantaneous=1
51-5
Constant TD
SG1 3P 24152
Float
4
R W n/a
0 - 9.9
51-5
Constant A
SG1 3P 24154
Float
4
R W n/a
0 - 600
51-5
Constant B
SG1 3P 24156
Float
4
R W n/a
0 - 25
51-5
Constant C
SG1 3P 24158
Float
4
R W n/a
0 - 1
51-5
Constant N
SG1 3P 24160
Float
4
R W n/a
0.5 - 2.5
51-5
Constant R
SG1 3P 24162
Float
4
R W n/a
0 - 30
51-5
Voltage Restraint Setpoint
SG1 3P 24164
Float
4
R W Volt
30 - 250
51-5
Voltage Restraint Mode
SG1 3P 24166
Uint32 4
R W n/a
Disabled=0
Control=1
Restraint=2
51-5
Alarm Configuration
SG1 3P 24168
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
51-5
Low-Line Scale
SG1 3P 24170
Float
4
R W n/a
0.001 - 3
51-5
Voltage Restraint Source
SG1 3P 24172
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-5
Constant Q
SG1 3P 24174
Float
4
R W n/a
0.1 - 10
51-5
Mode
SG2 1P 24176
Uint32 4
R W n/a
Disabled=0
IA=1
IB=2
IC=3
Imax=4
3I0=5
I2=6
IG=7
I1=8
51-5
Source
SG2 1P 24178
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-5
Pickup
SG2 1P 24180
Float
4
R W Amp
0.9 - 7.75