Legacy Register Table
Register
Description
Type
Units
Scaling Factor R/W
Range
43456
Battery Charge Failed Contact Input
Int32 n/a
n/a
RW
-1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16
43458
Battery Charge Failed Config Type
Int32 n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
43460
Battery Charge Failed Time Delay
Int32 Second n/a
RW
0 - 300
43462
Fuel Leak Detect Contact Input
Int32 n/a
n/a
RW
-1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16
43464
Fuel Leak Detect Config Type
Int32 n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
43466
Fuel Leak Detect Time Delay
Int32 Second n/a
RW
0 - 300
43468
User Configurable Input 1 Eng Run Only
Int32 n/a
n/a
RW
0 = Always
1 = While Engine Running Only
43470
User Configurable Input 2 Eng Run Only
Int32 n/a
n/a
RW
0 = Always
1 = While Engine Running Only
43472
User Configurable Input 3 Eng Run Only
Int32 n/a
n/a
RW
0 = Always
1 = While Engine Running Only
43474
User Configurable Input 4 Eng Run Only
Int32 n/a
n/a
RW
0 = Always
1 = While Engine Running Only
43476
User Configurable Input 5 Eng Run Only
Int32 n/a
n/a
RW
0 = Always
1 = While Engine Running Only
43478
User Configurable Input 6 Eng Run Only
Int32 n/a
n/a
RW
0 = Always
1 = While Engine Running Only
43480
User Configurable Input 7 Eng Run Only
Int32 n/a
n/a
RW
0 = Always
1 = While Engine Running Only
43482
User Configurable Input 8 Eng Run Only
Int32 n/a
n/a
RW
0 = Always
1 = While Engine Running Only
43484
User Configurable Input 9 Eng Run Only
Int32 n/a
n/a
RW
0 = Always
1 = While Engine Running Only
43486
User Configurable Input 10 Eng Run Only
Int32 n/a
n/a
RW
0 = Always
1 = While Engine Running Only
43488
User Configurable Input 11 Eng Run Only
Int32 n/a
n/a
RW
0 = Always
1 = While Engine Running Only
43490
User Configurable Input 12 Eng Run Only
Int32 n/a
n/a
RW
0 = Always
1 = While Engine Running Only
43492
User Configurable Input 13 Eng Run Only
Int32 n/a
n/a
RW
0 = Always
1 = While Engine Running Only
43494
User Configurable Input 14 Eng Run Only
Int32 n/a
n/a
RW
0 = Always
1 = While Engine Running Only
43496
User Configurable Input 15 Eng Run Only
Int32 n/a
n/a
RW
0 = Always
1 = While Engine Running Only
43498
User Configurable Input 16 Eng Run Only
Int32 n/a
n/a
RW
0 = Always
1 = While Engine Running Only
System Configuration and Status
Register
Description
Type
Units
Scaling Factor
R/W
Range
43500
Rated Volts
Float
Volt
n/a
RW
1 - 99999